Space heating supply and return. 1 1 1.5 2 2.5<br />

Steam and condensate lines. 2 3 3 4 4<br />

Cooling tower/condenser water<br />

supply to heat exchangers<br />

(where below 60°F).<br />

Project No.: 10145<br />

550 15 th Street Dual Brand Hotel<br />

03/16/2012<br />

1 1 1 1 1<br />

Cooling tower water piping<br />

exposed to weather.<br />

2 2 2 2 2<br />

Cooling tower make-up water<br />

piping exposed to weather.<br />

2 2 2 2 2<br />

Refrigerant suction and hot gas<br />

lines.<br />

1 1 1 1 1<br />

Fire protection piping exposed to<br />

weather.<br />

2 2 2 2 2<br />

Note: For any piping not noted above to be exposed to outdoor ambient<br />

temperatures, increase insulation thickness by 0.5 inches where installed in such<br />

exposed locations.<br />

B. All portions of Exhaust Piping for emergency generators and fire pumps, including fittings<br />

and silencers, shall be insulated as follows:<br />

1. For temperatures up to 1200 deg. F, provide 4” thick calcium silicate insulation,<br />

Specification “C”.<br />

2. For temperatures above 1200 deg. F, provide 4” thick thermal ceramic insulation,<br />

Specification “D”.<br />

3.03 DUCTWORK SYSTEM INSULATION:<br />

A. Ductwork on which insulation is not required:<br />

1. Fibrous glass ductwork.<br />

2. Lined ductwork.<br />

3. Exhaust air ductwork, except as specifically noted on drawings.<br />

B. Insulate each ductwork system specified in Table 2 with the type and thickness of insulation shown; omit<br />

insulation where ductwork is specified to be lined.<br />

Table 2<br />

Ductwork Insulation Schedule<br />

System Specification Vapor Seal Required<br />

HVAC Supply – concealed C Yes<br />

HVAC Return – concealed C No<br />

23 0713 - 6 MECHANICAL INSULATION