Project No.: 10145<br />

550 15th Street Dual Brand Hotel<br />

03/16/2012<br />

a. Copper phosphorus – BCuP.<br />

b. Silver – BAg<br />

D. Gaskets for Flanged Joints: ANSI B16.21; full-faced for cast-iron flanges; raised-face for<br />

steel flanges, unless otherwise indicated.<br />

E. Piping Connectors for Dissimilar Non-Pressure Pipe: Elastomeric annular ring insert, or<br />

elastomeric flexible coupling secured at each end with stainless steel clamps, sized for<br />

exact fit to pipe ends and subject to approval by plumbing code.<br />

F. Pipe Thread Sealant Material: Except as otherwise indicated, provide all pipe threads with<br />

the sealant material as recommended by the manufacturer for the service.<br />

2.08 PIPING APPLICATION:<br />

1. Manufacturer: Subject to compliance with requirements, provide piping thread<br />

sealant material. “Tyte-Unyte” for general use and Acorn no. 3500 for cleanouts.<br />

A. Natural Gas Piping:<br />

1. Above Grade:<br />

a. Exposed locations:<br />

i. 2” and smaller: Schedule 40 black steel pipe, beveled ends, with<br />

150 psi malleable iron fittings and threaded joints.<br />

ii. Larger than 2”: Schedule 40 black steel pipe with seamless steel<br />

butt-weld fittings and welded joints.<br />

b. Inaccessible Locations:<br />

2. Below Grade:<br />

i. All sizes: Schedule 40 seamless black steel pipe, beveled ends,<br />

with socket-weld fittings same thickness as pipe, and welded<br />

joints.<br />

a. Within Building: Schedule 40 seamless black steel with 150 psi forged<br />

steel fittings and welded joints. Provide piping with machine-applied<br />

coating and wrapping in accordance with local code and utility company<br />

requirements. Provide cathodic protection as called for on the drawings.<br />

b. Outside of Building: Polyethylene (PE) pipe, as approved by local utility<br />

company and code authorities having jurisdiction.<br />

B. Space Heating Water, Chilled Water, and Condenser Water Piping:<br />

1. 2-1/2” and smaller:<br />

a. Schedule 40 black steel with 150 psi malleable iron threaded fittings; or<br />

Type L copper tube, ASTM B-88, with wrought copper or bronze fittings<br />

per ANSI B16.22, brazed or lead-free soldered.<br />

2. 3” and larger:<br />

23 2113 - 8 HYDRONIC PIPING