D. <strong>Construction</strong>: ASME construction for 125 psi design pressure at 300 deg. F.<br />

2.03 WATER-TO-WATER PLATE HEAT EXCHANGER:<br />

A. This Contractor shall provide plate heat exchanger of capacity as scheduled and where<br />

shown on the drawings with embossed heat transfer plates, perimeter gaskets, guide rails,<br />

and frames and compression bolts.<br />

B. Units shall be ASME rated for 125 psig operating pressure, 300 deg. F. maximum<br />

temperature, have a heat transfer area to be produce the conditions scheduled on the<br />

drawing.<br />

C. Plates shall be Type 316L stainless steel and copper brazed.<br />

D. Nozzles shall be 150 lb. ASA rated loose flange type, of the size called for on the<br />

drawings.<br />

PART 3 – EXECUTION<br />

3.01 INSPECTION:<br />

A. Examine areas and conditions under which heat exchangers are to be installed. Do not<br />

proceed with work until unsatisfactory conditions have been corrected in manner<br />

acceptable to Installer.<br />

3.02 WATER-TO-WATER U-TUBE HEAT EXCHANGERS:<br />

A. General- Install water-to-water U-tube heat exchangers as indicated, and as specified<br />

herein.<br />

B. Mounting: Mount heat exchangers on steel floor stands as indicated, located for required<br />

clearance for tube bundle removal.<br />

C. Mounting: Mount heat exchangers on trapeze hangers as indicated, located for required<br />

clearance for tube bundle removal.<br />

D. Water Piping: Provide piping as indicated, including union, shutoff valve, and<br />

thermometer on each inlet and outlet connection; relief valve on tube bundle outlet, with<br />

outlet piped to floor drain; and ½” drain valve on shell drain connection.<br />

3.03 INSTALLATION OF WATER-TO-WATER PLATE AND FRAME HEAT EXCHANGERS:<br />

A. General: Comply with water-to-water plate and frame heat exchanger manufacturer's<br />

instructions for installation.<br />

B. Install water-to-water plate and frame heat exchangers, piping and accessories in<br />

accordance with manufacturer's instructions.<br />

Project No.: 10145<br />

550 15 th Street Dual Brand Hotel<br />

03/16/2012<br />

22 3500 - 3 DOMESTIC WATER HEAT<br />

EXCHANGERS