PART 3 – EXECUTION<br />

3.01 TEST AND TEST DATA:<br />

A. A factory load test shall be performed on each motor of 1000 watt input or greater to<br />

assure compliance with the energy-efficiency section of this specification.<br />

B. Typical test data on every motor to be used on this project shall be made available upon<br />

<strong>request</strong>.<br />

3.02 INSTALLATION:<br />

A. Install motors on motor mounting systems in accordance with motor manufacturer's<br />

instructions, securely anchored to resist torque, drive thrusts, and other external forces<br />

inherent in mechanical work. Secure sheaves and other drive units to motor shafts with<br />

keys and Allen set screws. For motors of 1/3 hp and less, sheaves and drive components<br />

may be secured with Allen set screws on flat surface of shaft. Unless otherwise indicated,<br />

set motor shafts parallel with machine shafts.<br />

B. Deliver starters and wiring devices which have not been factory-installed on equipment to<br />

electrical installer for installation.<br />

C. Install power and control connections for motors to comply with NEC and applicable<br />

provisions of Division 26 sections. Install grounding except where non-grounded isolation<br />

of motor is indicated.<br />

D. Provide 4” high concrete housekeeping pad for floor-mounted variable frequency drives.<br />

E. Where a separate disconnect switch is provided in the motor feeders between a VFD and<br />

the motor, provide an end switch at the disconnect to open the remote interlock shutdown<br />

circuit power circuit.<br />

3.03 VFD START-UP SERVICES:<br />

A. The variable frequency drive (VFD) vendor shall provide, as a minimum, the following<br />

services:<br />

1. Service of certified factory-trained representative to supervise startup, adjustment,<br />

and fine-tuning of all VFD’s and to instruct Owner on proper operation and<br />

maintenance procedures.<br />

2. Training of user personnel in basic troubleshooting. Training shall be on-site,<br />

shall be a minimum of 1 day's duration, and shall be performed in addition to<br />

startup of system.<br />

3. Each VFD manufacturer shall have a local representative specifically trained in<br />

troubleshooting, service and repair of its VFD’s. A statement of the length and<br />

extent of experience of the local service organization shall be included with the<br />

submittals.<br />

3.04 VFD HARMONIC DISTORTION TESTING:<br />

Project No.: 10145<br />

550 15 th Street Dual Brand Hotel<br />

03/16/2012<br />

23 0513 - 11 MECHANICAL/ELECTRICAL REQ.<br />

FOR MECHANICAL EQUIPMENT