2.02 CEILING AIR DIFFUSERS:<br />

Project No.: 10145<br />

550 15 th Street Dual Brand Hotel<br />

03/16/2012<br />

h. Greenheck<br />

i. Vent Products<br />

A. General: Except as otherwise indicated, provide manufacturer’s standard ceiling air<br />

diffusers where shown; of sizes, shapes, capacities and types indicated; constructed of<br />

materials and components as indicated; and as required for complete installation.<br />

B. Performance: Provide ceiling air diffusers that have, as minimum, throw and drop, and<br />

noise criteria ratings for each size device as listed in manufacturer's current data.<br />

C. Ceiling Compatibility: Provide diffusers with border styles that are compatible with adjacent<br />

ceiling systems, and that are specifically manufactured to fit into ceiling module with<br />

accurate fit and adequate support. Refer to general construction drawings and<br />

specifications for types of ceiling systems which will contain each type of ceiling air diffuser.<br />

D. Types: Provide ceiling diffusers of types, capacities, and with accessories and finishes as<br />

listed on air device schedule.<br />

1. All linear slot diffusers shall have air pattern control vanes, capable of 180º air<br />

pattern adjustment, and internally lined plenum boot, except as otherwise indicated<br />

or scheduled.<br />

E. Dampers: Volume dampers shall not be provided at diffuser necks unless otherwise<br />

specifically indicated or scheduled.<br />

2.03 REGISTERS AND GRILLES:<br />

A. General: Except as otherwise indicated, provide manufacturer's standard registers and<br />

grilles where shown; of sizes, shapes, capacities and types indicated; constructed of<br />

materials and components as indicated; and as required for complete installation.<br />

B. Performance: Provide registers and grilles that have, as minimum, throw and drop, and<br />

noise criteria ratings for each size device as listed in manufacturer's current data.<br />

C. Wall/Ceiling/Floor Compatibility: Provide registers and grilles with border styles that are<br />

compatible with adjacent wall/ceiling/floor systems, and that are specifically manufactured<br />

to fit into wall/ceiling/floor construction with accurate fit and adequate support. Refer to<br />

general construction drawings and specifications for types of wall/ceiling/floor construction<br />

which will contain each type of wall/ceiling/floor register and grille.<br />

D. Types: Provide registers and grilles of types, capacities, and with accessories and finishes as<br />

listed on air device schedule.<br />

1. All sidewall-type supply air registers shall be double deflection adjustable blade<br />

type, except as otherwise indicated or scheduled.<br />

2. All sidewall-type return and exhaust registers shall be 35º fixed blade type, except<br />

as otherwise indicated or scheduled.<br />

23 3713 - 3 DIFFUSERS, REGISTERS, AND<br />

GRILLES