2.02 AIR TERMINALS:<br />

Project No.: 10145<br />

550 15 th Street Dual Brand Hotel<br />

03/16/2012<br />

c. Carrier<br />

d. Environmental Technologies<br />

e. Krueger<br />

f. Metal-Aire<br />

g. Titus<br />

h. Trane<br />

A. General: Provide factory-fabricated and tested air terminals as indicated, selected with<br />

performance characteristics which match or exceed those indicated on schedule.<br />

B. Air terminal units shall be of low pressure drop design, single-duct throttling-type,<br />

pressure-independent, and suitable for use in medium pressure variable volume air<br />

distribution systems.<br />

C. Casing shall be of minimum 22-gauge galvanized steel construction, with internal<br />

acoustical, coated, ½” thick, 1-½ lb./cu. ft. density fiberglass insulation and inlet and<br />

outlet duct connections. Gasketed and insulated quick-opening access doors shall be<br />

provided for air terminals with internally mounted serviceable components, including<br />

actuators and fan motors. Access doors shall allow for removal of fan and/or servicing of<br />

unit without disturbing ductwork and piping connections.<br />

D. Internal air volume damper blade shall be of extruded aluminum or 18-gauge steel with<br />

keyed fit shaft and nylon bushing. Damper shall be constructed to prevent air leakage in<br />

excess of 2% of rated air quantity at 4.0” w.g. inlet static pressure. All mechanical parts<br />

shall be galvanized or non-ferrous.<br />

E. Hot water heating coils shall be designed for 200 psig maximum working pressure and<br />

200°F maximum operating temperature. Coils shall be serpentine-type, constructed of ½”<br />

O.D. copper tubes mechanically bonded to aluminum fins, with galvanized steel casting.<br />

F. Electric heating coils shall be constructed of electric resistance heating elements in a<br />

galvanized steel casing with integral control panel housed in a NEMA 1 enclosure, with<br />

hinged access door and factory wiring. Coils shall include primary automatic reset<br />

thermal cutout, secondary manual reset thermal cutout, line fuses, differential pressure air<br />

flow switch, door interlocking disconnect, magnetic contactors, terminal blocks for power<br />

and control connections, and UL listing as a duct heater. Provide a minimum of two<br />

stages for heaters 3 KW and above, except as otherwise indicated on drawings or<br />

schedules.<br />

G. All terminal units with electrical components shall be provided with a single-point electrical<br />

connection for the entire unit. All electrical components shall be UL listed and installed in<br />

accordance with the National Electrical Code.<br />

1. All line voltage electrical components shall be mounted in a NEMA 1 enclosure.<br />

2. The entire assembly shall be UL or ETL listed.<br />

3. Class II, 24V (AC), 40 VA transformer shall be provided for control power.<br />

H. Each terminal unit shall be provided with labeling showing plan designation, unit location,<br />

unit size, cfm range and settings, damper fail position, thermostat action, and calibration<br />

chart.<br />

23 3600 - 3 AIR TERMINAL UNITS