B. <strong>Construction</strong> shall be modular, consisting of removable panels with permanently affixed<br />

fasteners. Base pans shall be formed out of a minimum of 16 gauge G90 galvanized steel with<br />

floor mounting support channels. The condensate drain pan under the evaporator shall be epoxy<br />

coated galvanized steel. The compressor and controls shall be located in a compartment out of<br />

the air stream. Surfaces adjacent to the coil compartment shall be insulated with insulation to<br />

prevent condensation.<br />

C. The unit shall be of horizontal design. The supply air discharge shall be horizontal.<br />

D. Hinged Access Doors shall be provided at the openings for Compressor, Electrical Panel,<br />

Blowers, Motors and Drives. Doors shall be double-wall, insulated, mounted on a continuous<br />

piano hinge, secured with latches and sealed against a rigid steel frame with hollow-bulb rubber<br />

gasket material.<br />

2.4 COMPRESSOR<br />

A. The compressor shall be high-efficiency scroll type operating at scheduled voltage, phase, and<br />

frequency.<br />

B. The suction gas cooled compressor shall be equipped with thermal overload protection and a<br />

crankcase heater to prevent refrigerant migration to the compressor oil during shutdown.<br />

C. Provide a compressor sound jacket consisting of reinforced vinyl sewn around a 2 pound density<br />

fiberglass blanket to provide acoustical attenuation.<br />

2.5 FILTER RACK AND FILTERS<br />

A. The dehumidification unit shall include a weather tight air filter section with a duct flange and<br />

access door for side loading of filters. The filters shall be Class II, two inch, throw away.<br />

2.6 REFRIGERANT<br />

A. The refrigerant shall be R-410A.<br />

2.7 FAN<br />

A. The fan shall be a forward-curved, centrifugal blower. The wheel shall be dynamically balanced<br />

and installed on a steel shaft. The blower scroll and housing shall be constructed of cold-rolled<br />

steel, coated with an electrostatically applied acrylic enamel paint or G90 galvanized steel.<br />

B. The fan shall operate at the scheduled supply air CFM, outside air CFM (if equipped with this<br />

option) and W.C. external static pressure (ESP).<br />

2.8 FAN MOTOR<br />

A. The class B winding fan motor shall be belt drive. The motor shall comply with the efficiency<br />

requirements of EPACT-92. The belt drive assembly shall include a single “A” or “B” section belt<br />

and an adjustable motor sheave or double “B” section belt and non-adjustable motor sheave<br />

Project No.: 10145<br />

550 15 th Street Dual Brand Hotel<br />

03/16/2012<br />

23 8416 - 4 MECHANICAL DEHUMIDIFICATION<br />

UNITS