Project No.: 10145<br />

550 15 th Street Dual Brand Hotel<br />

03/16/2012<br />

d. Duro Dyne Corp.<br />

e. Environmental Elements Corp., Subs. of Koppers Co., Inc.<br />

f. Hart & Cooley Mfg. Co.<br />

4. Duct Hardware:<br />

a. Ventfabrics, Inc.<br />

b. Young Regulator Co.<br />

5. Duct Access Doors:<br />

a. Kess<br />

b. Greenheck<br />

c. Flexmaster (Inspector Series)<br />

d. Cesco-Advanced Air<br />

e. Duro Dyne Corp.<br />

f. Ventfabrics, Inc.<br />

6. Flexible Connections:<br />

a. Duro Dyne Corp.<br />

b. Ventfabrics, Inc.<br />

c. General Rubber Corp. (Process Exhaust Only)<br />

7. Constant Velocity Exhaust Fan Dampers:<br />

2.02 MANUAL VOLUME DAMPERS:<br />

a. American Warming and Ventilating<br />

A. Low Pressure Rectangular Dampers (less than 2000 FPM and under 4” W.C. S.P.<br />

Differential):<br />

1. For 12” in height or larger, use multiple opposed blade type and close fitted to<br />

ducts. The frame and blades shall be constructed of 16 ga. galvanized steel with<br />

carbon steel shaft mounted with oil-impregnated bronze/stainless steel bearings.<br />

Dampers shall be fitted with aluminum/stainless steel jamb seals and dual<br />

durometer vinyl/silicone blade edge seals. Linkage shall be in-jamb fixed type<br />

located outside the air stream and made of plated steel tie bar and crank plates,<br />

with stainless steel pivots. / on-blade fixed type located within the air stream and<br />

made of galvanized steel interconnected with plated steel brackets and pivots.<br />

Damper panels shall not exceed 48” wide. Provide jack shafting when duct size<br />

required is greater than 48” wide. Provide notched shaft end indicating damper<br />

position, locking quadrant to fix damper position, and handle. For flat oval and<br />

round ductwork, provide type C housing.<br />

2. For ducts less than 12” in height, frame shall be 16 ga. galvanized steel, with 20<br />

ga. galvanized steel blades, steel axle with nylon bearings, locking quadrant<br />

handle, and notched shaft end indicating damper position.<br />

OR<br />

Aluminum frame with stainless steel bearings.<br />

23 3300 - 3 AIR DUCT ACCESSORIES