Project No.: 10145<br />

550 15 th Street Dual Brand Hotel<br />

03/16/2012<br />

submitted by the VFD manufacturer with the submittal package, which<br />

includes all harmonics up to the 50th. Analysis shall include computergenerated<br />

waveforms, a statement of all assumptions, a one-line diagram<br />

of the system as analyzed, and a spectrum analysis showing individual<br />

harmonics along with a statement showing compliance with the<br />

standards.<br />

4. Manufacturer shall guarantee that harmonic voltage and current distortion on the<br />

line side (input terminals) of the VFD does not exceed 5% total voltage harmonic<br />

distortion and 15% total current harmonic distortion.<br />

5. Comply with FCC Subpart J of Part 15 for Class A computing devices from 7 MHz<br />

to 30 MHz for conduction limit without external modification.<br />

6. Output Power: Three-phase, 1.5 to 60 Hz, with variable voltage to provide proper<br />

and efficient operation of variable torque load, and capable of providing up to<br />

110% startup torque.<br />

7. Overload capacity minimum of 110% for 1 minute.<br />

D. The VFD shall be operable in two modes. In the "HAND" mode, the unit shall start and run<br />

at a speed as set on the manual speed adjuster. In the "AUTO" mode, the unit shall start<br />

in response to a contact closure and run at a speed established by a remote analog<br />

control signal.<br />

E. Minimum Requirements for Control Operation and Service:<br />

1. Door-interlocked disconnect switch (or MCB, 65,000 AIC minimum) for the entire<br />

unit.<br />

2. Isolated 120 VAC control transformer<br />

3. Digital annunciated fault and limit functions for:<br />

a. Thermal overload relay trip.<br />

b. Microprocessor self-check function.<br />

c. Output overcurrent trip.<br />

d. DC bus overvoltage trip.<br />

e. Inverse time overload trip.<br />

f. Heat sink overtemperature trip.<br />

g. DC bus fuse open.<br />

h. DC bus overvoltage (regen. limit).<br />

i. Output ground fault.<br />

j. Output line-to-line fault.<br />

4. Last 8 faults shall be retained in memory for operator recall.<br />

5. Isolated Binary Input Circuits:<br />

a. External safety lockout device.<br />

b. Remote Run/Stop command.<br />

6. Isolated Binary Output Circuits:<br />

a. Remote VFD fault trip alarm.<br />

b. VFD Run/Stop status.<br />

c. VFD Auto/Manual mode status.<br />

7. Analog Output Signals:<br />

23 0513 - 8 MECHANICAL/ELECTRICAL REQ.<br />

FOR MECHANICAL EQUIPMENT