A. Provide factory-tested pumps, thoroughly cleaned and painted with one coat of machinery<br />

enamel prior to shipment.<br />

B. Provide all pumps of same type by the same manufacturer.<br />

C. Casings shall be fabricated in such a manner as to allow removal and replacement of<br />

impellers without necessity of disconnecting piping.<br />

D. Motors shall conform to NEMA Standard MG-1, general purpose, continuous duty, Design<br />

B (except Design C where required for high starting torque); single, multiple, or variable<br />

speed, with type of enclosure and electrical characteristics as indicated, and greaselubricated<br />

ball bearings.<br />

1. Motors shall be selected that are non-overloading within the full range of the<br />

pump performance curve.<br />

2. Motors shall be selected for continuous duty at site altitude; Class F insulation shall<br />

be provided where required to meet ambient/altitude operating requirements at<br />

1.0 service factor.<br />

3. Built-in overload protection shall be provided.<br />

E. All pump motors 1 HP or larger shall be of the high-efficiency type.<br />

F. Vibration: Pumps shall be factory balanced such that vibration amplitude, velocity, and<br />

acceleration values do not exceed ISO General Machinery Vibration Chart “Very Good”<br />

curves or manufacturer’s standards, whichever is more stringent.<br />

2.02 MANUFACTURERS:<br />

A. Manufacturer: Subject to compliance with requirements, provide products by one of the<br />

following in each category:<br />

1. In-Line Circulation Pumps:<br />

Project No.: 10145<br />

550 15 th Street Dual Brand Hotel<br />

03/16/2012<br />

a. Bell & Gossett ITT, Fluid Handling Div.<br />

b. Grundfos Pumps Corp.<br />

c. Taco, Inc.<br />

d. Peerless Pumps<br />

e. Armstrong Pumps, Inc.<br />

f. Dunham-Bush, Inc.<br />

2. Water Pressure Booster Systems:<br />

a. Grundfos Pumps Corp.<br />

b. Bell & Gossett ITT, Fluid Handling Div.<br />

c. Syncroflo, Inc.<br />

d. Paco Pumps<br />

e. Armstrong Pumps, Inc.<br />

f. PSF, Div. of Messco, Inc.<br />

g. Peerless Pumps<br />

3. Pedestal Type Sump Pumps:<br />

a. Armstrong Pumps, Inc.<br />

221123 - 3 PLUMBING PUMPS