1. Alfa Laval Inc.<br />

2. API Heat Transfer Inc.<br />

3. APV; a brand of SPX Corporation.<br />

4. Armstrong Pumps, Inc.<br />

5. Delta T Heat Exchangers.<br />

6. ITT Corporation; Bell & Gossett.<br />

7. Mueller, Paul, Company.<br />

8. Polaris Plate Heat Exchangers.<br />

9. SEC Heat Exchangers.<br />

10. TACO Incorporated.<br />

11. Thermo Dynamics Ltd.<br />

12. Tranter, Inc.<br />

B. STANDARDS<br />

1. ASME Section II - Material Specification<br />

2. ASME Section V - Non-Destructive Testing<br />

3. ANSI B 16.5 - Flanged fittings<br />

4. ASME Section IX - Welding and brazing qualifications<br />

5. ASME Section VIII, Division I - Pressure Vessel Code<br />

6. OSHA<br />

C. CERTIFICATION<br />

1. Plate Heat Exchangers shall be designed, constructed and tested in accordance with<br />

Section VIII, Division I of the ASME Pressure Vessel Code, and shall be code stamped. CRN<br />

numbers are required for all vessels with Canadian destinations.<br />

2.3 MECHANICAL DESIGN REQUIREMENTS<br />

A. General<br />

1. The Plate Heat Exchanger Manufacturer shall not subcontract or purchase the plates for<br />

resale. He shall press his own patterns of plates.<br />

2. The Plate Heat Exchanger Manufacturer shall have an established and on-going<br />

3. QA/QC program including manuals available for inspection at plant.<br />

B. Frame Components<br />

1. Preference will be given to single pass designs with all connections on the fixed cover.<br />

2. The fixed and movable covers shall be of sufficient uniform thickness to withstand all<br />

loadings. Welded reinforcements or stiffeners are not permitted.<br />

3. The movable cover shall be provided with a roller bearing for units greater than 50" in<br />

height. This allows the cover to be moved with greater ease during plate inspection.<br />

4. The carrying and guide bars shall be designed to allow for a plate pack expansion of at<br />

least 10% while still providing maintenance space.<br />

5. The surfaces of the carrying and guide bars that come into contact with the plates shall be<br />

stainless steel. All carbon steel frame components (except bolts) shall be painted or zinc<br />

plated.<br />

6. The heat exchanger frame shall be of bolted construction. Welding of the pressure<br />

retaining components is not permitted.<br />

Project No.: 10145<br />

550 15th Street Dual Brand Hotel<br />

03/16/2012<br />

23 5700 - 3 HEAT EXCHANGERS FOR HVAC