1.03 FIRE HAZARD RATING:<br />

A. All insulation products (including insulation, jacket, and adhesive used to adhere the jacket<br />

to the insulation) shall have composite Fire and Smoke Hazard ratings, as tested under<br />

procedures defined by ASTM E-84, NFPA 255 and UL 723, not exceeding:<br />

Flame Spread 25<br />

Smoke Developed 50<br />

B. Accessories such as adhesives, mastics, cements and cloth for fittings shall have the same<br />

component ratings as listed above. Paper laminate jackets shall be permanently fire and<br />

smoke resistant. Chemicals used for treating paper in jacket laminates shall not be water<br />

soluble and shall be unaffected by water and humidity.<br />

1.04 SUBMITTALS:<br />

A. Product Data: Submit manufacturer's technical product data, installation instructions and<br />

maintenance requirements for each type of mechanical insulation. Submit schedule<br />

showing manufacturer's product number, k-value, thickness, density, and furnished<br />

accessories for each mechanical system requiring insulation. Submit detailed product<br />

information and installation information for all jacketing systems specified in this section.<br />

1.05 DELIVERY, STORAGE, AND HANDLING:<br />

A. Deliver insulation, coverings, cements, adhesives, and coatings to site in containers with<br />

manufacturer's stamp or label affixed, showing fire hazard indexes of products.<br />

1.06 PROTECTION:<br />

A. Protect insulation against dirt, water, chemical, or mechanical damage before, during, and<br />

after installation. Any such insulation or covering damaged prior to final acceptance of<br />

the work shall be satisfactorily replaced.<br />

PART 2 – PRODUCTS<br />

2.01 MANUFACTURERS:<br />

A. Manufacturer: Subject to compliance with requirements, provide product by one of the<br />

following in each category:<br />

1. Mechanical Insulation: Johns Manville; Owens-Corning Fiberglass Corp.;<br />

CertainTeed Corp.; Knauf Fiberglass; Manson; Armstrong World Industries Inc.;<br />

Pittsburgh Corning Corp.; PABCO, Inc.; Rubatex Corp.<br />

2. Jacketing & Covering Products: Childers; Ceel-Co; Zeston; Alpha Associates, Inc.<br />

2.02 PIPING INSULATION MATERIALS:<br />

A. Specification “A”, Fiberglass Piping Insulation: ASTM C-547, Class I or Class II unless<br />

otherwise indicated. “k” factor shall be maximum of 0.24 at 75° F mean temperature.<br />

Project No.: 10145<br />

550 15 th Street Dual Brand Hotel<br />

03/16/2012<br />

23 0713 - 2 MECHANICAL INSULATION