PART 1 – GENERAL<br />

1.01 DESCRIPTION OF WORK:<br />

Project No.: 10145<br />

550 15 th Street Dual Brand Hotel<br />

03/16/2012<br />

SECTION 23 3113<br />

METAL DUCTS<br />

A. Extent of metal ductwork is indicated on drawings and in schedules, and by requirements<br />

of this Section.<br />

DUCT SERVICE TYPE/CONSTRUCTION<br />

Supply air between fans and terminal units<br />

(medium and high pressure).<br />

Supply air from discharge of terminal units/fans<br />

to air devices (low pressure).<br />

Galvanized steel; spiral, round, oval, or<br />

rectangular (lined where noted on drawings);<br />

factory fabricated.<br />

Galvanized sheet metal; spiral, round, oval or<br />

rectangular (lined where noted on drawings);<br />

factory or shop fabricated.<br />

Return air ductwork. Galvanized sheet metal (lined where noted on<br />

drawings); factory or shop fabricated.<br />

General building exhaust. Galvanized sheet metal (lined where noted on<br />

drawings); factory or shop fabricated.<br />

Transfer ducts. Galvanized sheet metal, internally lined, as<br />

described above for low-pressure supply;<br />

factory or shop fabricated.<br />

Sound elbows for R.A. grilles Galvanized sheet metal (internally lined).<br />

OR<br />

Fibrous glass ductboard.<br />

Outdoor air intake ductwork. Galvanized sheet metal, rectangular; factory or<br />

shop fabricated.<br />

Exterior uninsulated ductwork. Aluminum, 304 SS, or painted galvanized steel.<br />

Pool room supply/Exhaust, Shower, locker room Aluminum with silicone sealant.<br />

exhaust.<br />

B. Exterior insulation of metal ductwork is specified in other Division 23 sections, and is<br />

included as work of this section.<br />

C. Refer to other Division 23 sections for ductwork accessories.<br />

D. Refer to other Division 23 sections for fans and air handling units.<br />

E. Refer to other Division 23 sections for testing, adjusting, and balancing of metal ductwork<br />

systems.<br />

1.02 DEFINITIONS:<br />

A. Low Pressure Duct: Duct required by the drawings, specifications, or referenced standards<br />