Project No.: 10145<br />

550 15 th Street Dual Brand Hotel<br />

03/16/2012<br />

a. 4-20 mA or 0-10 vdc output for VFD speed.<br />

b. 4-20 mA or 0-10 vdc output for VFD load.<br />

F. Minimum Required Standard Features:<br />

1. Door-mounted or visible components:<br />

a. Power-on light.<br />

b. Safety lockout indication.<br />

c. Inverter run indication.<br />

d. Bypass run light.<br />

e. VFD fault indication.<br />

f. 32-Character (minimum) alphanumeric liquid crystal display.<br />

g. Input keypad for parameter input and display selection.<br />

h. Manual speed adjustment means.<br />

i. Hand/Off/Auto VFD selector.<br />

2. Furnish only non-filament type indicating lights.<br />

3. Provide the following features:<br />

a. Adjustable current limit circuit to prevent nuisance tripping during<br />

acceleration or run conditions.<br />

b. Active regeneration limit circuit to prevent nuisance overcurrent tripping<br />

during deceleration.<br />

c. Input power single phasing and/or reverse phasing protection.<br />

d. Minimum and maximum speed adjustments, separate and noninteractive.<br />

e. Power loss restart selectable for Auto Restart in auto mode only.<br />

f. Automatic restart from undervoltage, power failure, or control fault.<br />

g. Critical frequency lockout for up to 2 points, available from 10% to 100%<br />

speed with an adjustable band width.<br />

h. Provide I2t fuses or other protection for power-handling components.<br />

Control shall survive load side short circuits without component failure,<br />

and shall annunciate output phase-to-phase and phase-to-ground faults.<br />

i. Volts-per-hertz ratio shall be automatic, tracking motor load requirements<br />

to achieve most efficient operation within the parameters selected.<br />

4. To reduce possible acoustical noise and electrical interference, drive control shall<br />

have an automatically variable carrier frequency of at least 800 to 2,500 hertz.<br />

There shall be no sudden frequency shifts which cause acoustical noise increases<br />

during shifts in the motor.<br />

5. Control shall be capable of starting into a spinning motor, and also switching<br />

from inverter to bypass back to inverter without tripping off line. Control shall also<br />

be capable of stopping a motor rotating in the reverse direction and then<br />

accelerating that motor in the proper direction.<br />

6. Control shall have a 4 - 20 mADC or 0 - 10 VDC isolated instrument control<br />

signal follower. Isolation shall be either optical or transformer type. The<br />

manufacturer shall include documentation with submittals that confirm the<br />

follower is of the isolated type.<br />

7. All components shall be supplied in an integral NEMA 1 or better metal enclosure;<br />

separate enclosures are not allowed.<br />

8. All drives shall carry ETL or UL nationally recognized testing laboratory approval.<br />

23 0513 - 9 MECHANICAL/ELECTRICAL REQ.<br />

FOR MECHANICAL EQUIPMENT