PART 1 – GENERAL<br />

1.01 DESCRIPTION:<br />

Project No.: 10145<br />

550 15 th Street Dual Brand Hotel<br />

03/16/2012<br />

SECTION 23 2123<br />

HYDRONIC PUMPS<br />

A. This Section includes the furnishing and installation of HVAC pumps and accessories.<br />

Extent of HVAC pump work required by this Section is indicated on drawings and<br />

schedules, and by requirements of this Section.<br />

B. Types of pumps specified in this Section include the following:<br />

1. Vertical In-Line<br />

2. Frame-Mounted End Suction<br />

C. Refer to other Division 23 sections for other work that is not work of this Section.<br />

D. Provide the following electrical work as work of this Section, complying with requirements<br />

of Division 26 sections:<br />

1.02 QUALITY ASSURANCE:<br />

1. Control wiring between field-installed controls, indicating devices, and pump<br />

control panels.<br />

a. Control wiring specified as work of Division 23 for Automatic Temperature<br />

Controls is work of that section.<br />

A. Hydraulic Institute Compliance: Design, manufacture and installation of HVAC pumps<br />

shall be in accordance with “Hydraulic Institute Standards.”<br />

B. UL Compliance: Provide HVAC pumps that are listed and labeled by UL and comply with<br />

UL Standard 778 “Motor Operated Water Pumps.”<br />

C. All pump motors shall be NEMA rated and UL listed.<br />

D. Nameplates showing pump manufacturer’s name, model and/or serial number, impeller<br />

size, and motor data shall be clearly visible. If impeller has been trimmed from standard<br />

size, this information shall appear on the nameplate also.<br />

E. Certified performance data including vibration criteria shall be furnished for all custom<br />

and non-cataloged pumps.<br />

F. Standards:<br />

1. Hydraulic Institute (HI)<br />

2. American National Standards Institute (ANSI)<br />

3. American Society of Mechanical Engineers (ASME)<br />

4. American Society for Testing and Materials (ASTM)<br />

23 2123 - 1 HYDRONIC PUMPS