25.12.2012 Views

substitution request - Alliance Construction Solutions

substitution request - Alliance Construction Solutions

substitution request - Alliance Construction Solutions

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Project No.: 10145<br />

550 15 th Street Dual Brand Hotel<br />

03/16/2012<br />

i. Noise Rating: NEMA standard (90 dBA maximum for single or two-pole,<br />

85 dBA maximum for three-pole).<br />

i. Motor Connections: Flexible conduit, except where plug-in<br />

electrical cords are specifically indicated or furnished as OEM<br />

equipment with motor.<br />

Motor<br />

Horse-<br />

Power Open Motors, ODP Enclosed Motors, TEFC<br />

1200 RPM 1800 RPM 3600 RPM 1200 RPM 1800 RPM 3600 RPM<br />

1 80.0 82.5 - 80.0 82.5 75.5<br />

1.5 84.0 84.0 82.5 85.5 84.0 82.5<br />

2 85.5 84.0 84.0 86.5 84.0 84.0<br />

3 85.5 86.5 84.0 87.5 87.5 85.5<br />

5 87.5 87.5 85.5 87.5 87.5 87.5<br />

7.5 88.5 88.5 87.5 89.5 89.5 88.5<br />

10 90.2 89.5 88.5 89.5 89.5 89.5<br />

15 90.2 91.0 89.5 90.2 91.0 90.2<br />

20 91.0 91.0 90.2 90.2 91.0 90.2<br />

25 91.7 91.7 91.0 91.7 92.4 91.0<br />

30 92.4 92.4 91.0 91.7 92.4 91.0<br />

40 93.0 93.0 91.7 93.0 93.0 91.7<br />

50 93.0 93.0 91.4 93.0 93.0 92.4<br />

60 93.6 93.6 93.0 93.6 93.6 93.0<br />

75 93.6 94.1 93.0 93.6 94.1 93.0<br />

100 94.1 94.1 93.0 94.1 94.5 93.6<br />

125 94.1 94.5 93.6 94.1 94.5 94.5<br />

150 94.5 95.0 93.6 95.0 95.0 94.5<br />

200 94.5 95.0 94.5 95.0 95.0 95.0<br />

(Table 1-cont’d ↑)<br />

Note: For other types of motors, including, but not limited to, multi-speed motors, explosion proof<br />

motors and/or special hermetic motors packaged with equipment, efficiency and power factors<br />

may vary from above values. For these special applications, motors shall be high-efficiency type<br />

and are subject to review by the Engineer.<br />

B. Inverter Duty Motors:<br />

Nominal Full-Load Efficiency (Table 1)<br />

1. Motors 7-1/2 HP and larger supplied for use with Variable Frequency Drive (VFD)<br />

shall be rated for inverter duty and must include a stainless steel nameplate for<br />

identification as “Inverter Duty Motor.”<br />

2. Nameplate shall also show that motor is suitable for variable torque operation on<br />

VFD power from 6 to 60 hz and show rated torque in lb-ft on inverter power in<br />

addition to the standard nameplate data specified in NEMA standards.<br />

23 0513 - 4 MECHANICAL/ELECTRICAL REQ.<br />

FOR MECHANICAL EQUIPMENT