A. Applicable Codes and Standards:<br />

1. The International Building Code (IBC) as published by the International<br />

Conference of Building officials.<br />

2. All State and Local Codes.<br />

3. ASHRAE HVAC Applications Handbook, Sound and Vibration Control.<br />

1.05 MANUFACTURER'S RESPONSIBILITY:<br />

A. Manufacturer of vibration isolation equipment shall have the following responsibilities:<br />

1.06 RELATED WORK:<br />

1. Determine vibration isolator sizes and locations.<br />

2. Provide vibration isolation units as scheduled or otherwise specified.<br />

3. Provide installation instructions, drawings and trained field supervision to ensure<br />

proper installation and performance.<br />

A. Housekeeping Pads: Details and design of housekeeping pad reinforcement and<br />

monolithic pad attachment to the structure shall be prepared by the contractor if not<br />

already indicated on the drawings.<br />

B. Supplementary Support Steel: Contractor shall supply supplementary support steel for all<br />

equipment, piping, ductwork, etc., including roof mounted equipment, as required or<br />

specified.<br />

PART 2 – PRODUCTS<br />

2.01 ACCEPTABLE MANUFACTURERS:<br />

A. Manufacturer: Subject to compliance with requirements, provide products by the<br />

following:<br />

1. Mason Industries, Inc.<br />

B. Alternate Manufacturer: All vibration isolators described in this Section shall be the<br />

product of a single manufacturer. Mason Industries’ products are the basis of these<br />

specifications; products of other manufacturers are acceptable provided their systems<br />

strictly comply with these specifications and have been reviewed by the Engineer.<br />

Submittals and certification sheets shall be in accordance with Section 1.03.<br />

2.02 PRODUCT DESCRIPTIONS:<br />

A. The following product descriptions are listed by a letter, which is used as the identifier in<br />

the Equipment Vibration Isolation Schedule and elsewhere in Part 3 of this Specification.<br />

1. Mountings:<br />

Project No.: 10145<br />

550 15 th Street Dual Brand Hotel<br />

03/16/2012<br />

a. Specification “A”: Double deflection neoprene mountings shall have a<br />

minimum static deflection of 0.35”. All metal surfaces shall be neoprene<br />

23 0548 - 3 VIBRATION AND SEISMIC<br />

CONTROLS FOR HVAC PIPING<br />

AND EQUIPMENT