Insulation shall have jacket with tensile strength of 35 lbs/in and factory applied vapor<br />

barrier jacket with permeability of 0.02 perm with adhesive self-sealing lap joint.<br />

B. Specification “B”, Cellular Glass Piping Insulation: ASTM C-552, Type II, Class 2. “k”<br />

factor shall be maximum of 0.29 at 75° F mean temperature.<br />

C. Specification “C”, Calcium Silicate Piping Insulation: ASTM C-533, Type I. “k” factor shall<br />

be maximum of 0.45 at 500° F mean temperature, compression strength of 200 psi for<br />

5% compression, transverse strength of 200 psi for 5% compression, and minimum<br />

flexural strength of 60 psi.<br />

D. Specification “D”, Thermal Ceramic Insulation: “k” factor shall be a maximum of 1.5 at<br />

1500° F mean temperature, 2000° F temperature limit.<br />

E. Jackets for Piping Insulation: ASTM C-921, Type I for piping with temperatures below<br />

ambient, Type II for piping with temperatures above ambient. Type I may be used for all<br />

piping at Installers option.<br />

1. Fitting Covers: UV-resistant PVC, premolded, with maximum flame spread rating<br />

of 25 and maximum smoke developed rating of 50. Use PVC tape for cold<br />

systems, serrated tacks or PVC tape for hot systems.<br />

2. Aluminum Jacketing: Manufactured from T3003 (or T5005) H14 to H19<br />

aluminum alloy with 3/16” corrugations, and having a factory-attached 1 mil thick<br />

polyethylene moisture barrier continuously laminated across the full width of the<br />

jacketing. Jacketing shall be .016” thick minimum. Provide matching factoryfabricated<br />

covers for 90° and 45° elbows, tee fittings, flange fittings, valve bodies,<br />

blind ends, reducers and other fittings as necessary to make the covering system<br />

complete, waterproof and weatherproof.<br />

3. Cloth Jacketing Material: Not less than 8 oz. per square yard, with adhesives,<br />

cement and sealer as recommended by insulation manufacturer for the intended<br />

application. PVC premolded fitting covers shall not be provided.<br />

F. Piping Insulation Accessories: Provide staples, bands, wires, cements and similar<br />

accessories as recommended by insulation manufacturer for the applications indicated.<br />

G. Piping Insulation Compounds: Provide adhesives, sealers, protective finishes and similar<br />

compounds as recommended by insulation manufacturer for the applications indicated,<br />

and additional finishes as specified.<br />

2.03 DUCTWORK INSULATION MATERIALS:<br />

A. Specification “A”, Rigid Fiberglass Insulation Board, 2” thick: ASTM C-612, Class 1, 450°F<br />

temperature limit, density of 3 lbs. per cu. ft. "k" value shall be maximum of 0.23 at 75°F<br />

mean temperature, facing of 0.7 mil foil reinforced with glass mesh and laminated to 40<br />

lb kraft, with factory applied vapor barrier facing.<br />

B. Specification “B”, Round Surface Semi-Rigid Fiberglass Insulation, 1-1/2” thick: ATSM C-<br />

612, Class 1, 450°F temperature limit, 3 lbs. per cu. ft. density, "k" value of 0.25<br />

maximum at 75° F mean temperature and foil-skrim-kraft facing. Orientation of fibers<br />

shall be perpendicular to facing to facilitate application on round surfaces.<br />

C. Specification “C”, Flexible Fiberglass Ductwork Insulation, 1-1/2” thick, factory applied:<br />

ASTM C-553, Type I, 1.0 lb. per cu. ft. density. “k” value shall be maximum of 0.25 at<br />

Project No.: 10145<br />

550 15 th Street Dual Brand Hotel<br />

03/16/2012<br />

23 0713 - 3 MECHANICAL INSULATION