Project No.: 10145<br />

550 15 th Street Dual Brand Hotel<br />

03/16/2012<br />

functional surfaces; butterfly valves shall be shipped closed or slightly open; and<br />

swing check valves shall be blocked in either closed or open position.<br />

B. Storage: Use the following precautions during storage:<br />

1. Valves shall be stored and protected against all dirt, debris and foreign material at<br />

all times.<br />

2. Do not remove valve end protectors unless necessary for inspection; then reinstall<br />

for storage.<br />

3. Protect valves against weather. Where practical, store valves indoors. Maintain<br />

valve temperature higher than the ambient dew point temperature. If outdoor<br />

storage is necessary, support valves off the ground and protect in watertight<br />

enclosures.<br />

C. Handling: Valves whose size requires handling by a crane or lift shall be slung or rigged<br />

to avoid damage to exposed valve parts. Handwheels and stems shall not be used as<br />

lifting or rigging points.<br />

PART 2 – PRODUCTS<br />

2.01 MANUFACTURERS:<br />

A. Manufacturer: Subject to compliance with requirements, provide products by one of the<br />

following in each category:<br />

2.02 VALVE FEATURES:<br />

1. Gate Valves: Nibco, Stockham, Hammond, Milwaukee.<br />

2. Ball Valves: Apollo, Nibco, Watts, Milwaukee, Stockham, Anvil.<br />

3. Eccentric Plug Balancing Valves: Keystone/Tyco, Milliken, DeZurik.<br />

4. Globe Valves: Nibco, Stockham, Hammond, Milwaukee.<br />

5. Butterfly Valves: Keystone/Tyco, Nibco, Milwaukee, Apollo, Stockham, Anvil.<br />

6. Swing Check Valves: Nibco, Stockham, Watts (threaded), Apollo, Milwaukee,<br />

Anvil (grooved only).<br />

7. Non-Slam Check Valves: Nibco, Keystone/Tyco, Milwaukee, Stockham,<br />

Centerline, Val-Matic, Metraflex, Technocheck, Golden Anderson, Anvil.<br />

8. Lift Check Valves: Apollo, Nibco, Milwaukee, Metraflex, Stockham.<br />

9. Solenoid Valves: Magnatrol Valve Corp., Skinner, General Controls, Asco.<br />

A. General: Comply with MSS-92 1980 "Valve Users Manual."<br />

B. All valves of each type shall be of one manufacturer.<br />

C. Valve Design: Valves shall have rising stem, or rising stem outside screw and yoke design;<br />

except, non-rising stem valves may be used where headroom prevents full operation of<br />

rising stem valves.<br />

D. Sizes: Unless otherwise indicated, provide valves of same size as upstream pipe size.<br />

(Control valves shall be sized for required flow, 3 psi pressure drop maximum.)<br />

E. Operators: Provide the following special operator features:<br />

23 0523 - 2 GENERAL-DUTY VALVES FOR<br />

HVAC PIPING