depending upon motor horsepower for establishing the specified CFM. Single phase motors shall<br />

be capacitor start. The fan motor horsepower, voltage and frequency shall be as scheduled.<br />

2.9 EVAPORATOR (DEHUMIDIFICATION) COIL<br />

A. The coil shall be of adequate face area and rows to remove the specified amount of moisture<br />

from the air stream at specified conditions.<br />

B. The evaporator coil shall be constructed of aluminum fins mechanically bonded to copper tubes.<br />

The fins shall be acrylic-coated for added corrosion protection.<br />

2.10 AIR CONDENSER (AIR REHEAT) COIL<br />

A. The coil shall be of sufficient size to reject the required amount of total heat.<br />

B. The condenser coil shall be constructed of aluminum fins mechanically bonded to copper tubes.<br />

The fins shall be acrylic-coated for added corrosion protection.<br />

2.11 AUXILIARY AIR HOT WATER COIL<br />

A. The hot water coil shall be factory mounted after the air reheat condenser coil. The installing<br />

contractor shall install the control valve (by others) and pipe the hot water to the connections on<br />

the outside of the unit. The control device for the valve must be interlocked with the terminal strips<br />

in the unit.<br />

B. Coil shall be constructed of aluminum fins mechanically bonded to copper tubes. The fins shall<br />

be acrylic-coated for added corrosion protection.<br />

2.12 WATER CONDENSER (POOL HEATING)<br />

A. For recovering heat to pool water, the unit shall be equipped with a vented refrigerant-to-water,<br />

helically wound coaxial vented condenser sized to reject the required amount of heat. The water<br />

side tubing shall be constructed of cupronickel for corrosion protection. The maximum water<br />

pressure drop shall be as scheduled.<br />

2.13 CONTROL PANEL<br />

A. The control panel shall have a 4 line, 20 character LCD display, LED annunciators, and a 6<br />

button operator interface. The controller main board shall have all set points and program<br />

information stored in nonvolatile memory for protection from power failure.<br />

B. The control panel shall be wall or unit mounted. It shall be capable of being mounted up to 1000<br />

feet from the unit. All internal circuit boards shall be conformal coated. The control panel shall be<br />

connected to the unit by standard six wire RJ-25 phone cord. The control panel shall be capable<br />

of being directly connected to the unit for service convenience.<br />

C. The controller shall be micro-processor based. The following set points shall be programmable at<br />

the panel:<br />

Project No.: 10145<br />

550 15 th Street Dual Brand Hotel<br />

03/16/2012<br />

23 8416 - 5 MECHANICAL DEHUMIDIFICATION<br />

UNITS