Project No.: 10145<br />

550 15 th Street Dual Brand Hotel<br />

03/16/2012<br />

b. Ingersoll-Rand Co.<br />

c. Peerless Pump.<br />

d. Weil Pump Co.<br />

e. Weinman Pump LFE Corp., Fluids Control Div.<br />

4. Submersible Sump Pumps:<br />

2.03 IN-LINE CIRCULATION PUMPS:<br />

a. Hydromatic Pumps<br />

b. Goulds Pumps, Inc.<br />

c. Kenco Pump Div., American Crucible Products Co.<br />

d. Peabody Barnes.<br />

e. Weil Pump Co.<br />

f. Weinman Pump LFE Corp., Fluids Control Div.<br />

g. Zoeller Co.<br />

h. Peerless Pumps<br />

A. General: Provide in-line circulation pumps where indicated, and of capacities as<br />

scheduled.<br />

B. Type: Horizontal, oil-lubricated, designed for 125 psi working pressure, 225°F (107°C)<br />

continuous water temperature, and specifically designed for quiet operation.<br />

C. Body: Bronze or stainless steel construction.<br />

D. Shaft: Steel, ground and polished, with integral thrust collar.<br />

E. Bearings: Two horizontal sleeve bearings designed to circulate oil.<br />

F. Seal: Mechanical, with carbon seal face rotating against ceramic seat.<br />

G. Coupling: Self-aligning, flexible coupling.<br />

2.04 PEDESTAL TYPE SUMP PUMPS:<br />

A. General: Provide pedestal type sump pumps as indicated, of sizes and capacities as<br />

scheduled.<br />

B. Pump: Centrifugal, semi-open impeller type sump pump, complete with galvanized-steel<br />

strainer, cast-iron base plate, suction plate and casing, and cast-iron or bronze impeller.<br />

C. Shaft: Stainless steel of length to suit depth of basin, connected with flexible coupling to<br />

motor, and intermediate sleeve bearing for lengths over 4 ft.<br />

D. Motor: Open drip-proof, with electrical characteristics as scheduled.<br />

E. Basin: Fiberglass construction of indicated dimensions, with inlet connections of sizes and<br />

locations as indicated. Maintain minimum of 3 ft. depth below lowest inlet invert.<br />

F. Cover: Cast-iron or steel circular cover with manhole or handhole opening, depending on<br />

diameter. Provide openings for pump, control rod, and discharge piping.<br />

221123 - 4 PLUMBING PUMPS