2.12 SPECIALTIES:<br />

A. Foot Valve: Single/Double poppet constructed of plated cast iron/bronze body and bronze<br />

poppet with replaceable bronze seats and monel/galvanized brass 20/8 screen.<br />

OPW No. [ ]<br />

B. Float Vent Valve: Stainless steel ball with Duragard coated seat length determined by tank<br />

supplier.<br />

OPW No. 53-V series<br />

C. Fill/Spill Containers: Container shall consist of Duratuff lower body, cast iron<br />

cover/aluminum cover, polyethylene gravel guard, epoxy coated cast iron body ring, high<br />

density polyethylene bellows, acetal-polypropylene drain valve, stainless steel clamps,<br />

Buna-N seals with a nominal 3 gallon capacity,<br />

OPW #1.<br />

D. Vent Caps and Flame Arresters: Provide caps and arresters to melt local code and fire<br />

department requirements.<br />

2.13 FUEL OIL LEVEL-INDICATION AND LEAK DETECTION:<br />

A. General: The tank liquid level management system shall be a fully integrated<br />

microprocessor based system for 1 to 8 tanks. The system shall continuously monitor the<br />

liquid inventory of each tank. System shall include an individual selectable display for<br />

product level in inches, product volume in gallons, level of water, and temperature of<br />

product for each tank. The visual alarm condition shall be displayed until the condition is<br />

corrected. The system shall retain in memory the last 3 alarm conditions by tank and last<br />

10 deliveries by tank. The system shall include battery back-up to retain data stored in<br />

memory during loss or interruption of power for up to ten years. System shall monitor<br />

liquid levels and product temperature for tank leak test and/or theft test during tank<br />

quiescent periods. Inventory reports containing product levels, volumes, water level, and<br />

product temperatures, alarm history reports, delivery history reports, theft test results, and<br />

tank leak test results. Reports shall all be presented via a RS-232 data output port built-in<br />

printer. Reports shall include site name/location, date, and time. System shall operate on<br />

110-120 V., 60 hertz, A.C. current.<br />

B. Control Console: Control console shall be constructed in a wall-mountable steel enclosure<br />

complete with a 5 digit, 0.81, high, 7 segment LED display for inches and gallons of<br />

product of inventory, level of water and temperature of product. Control console shall<br />

include individual visual LED light and audible alarm for programmable high level, low<br />

level and water presence alarm conditions for each tank. Two alarm relays, reach rated<br />

SPDT-3 amps, shall be provided standard for external control functions. Provide<br />

additional alarm relays, two per tank (maximum of 16). Audible alarm shall include a<br />

disable switch. Touch key pad shall be splash proof dual purpose, accommodating tank<br />

and function selection as well as system programming functions. Control console<br />

calibration, set-up and diagnostic trouble shooting. The console should provide SPDT<br />

switch contacts rated 3 AMPS at 120 VAC, for each leak sensor, for controlling external<br />

devices. Electrical circuitry to tank mounted sensors should be low current rated<br />

intrinsically safe for hazardous areas.<br />

Project No.: 10145<br />

550 15 th Street Dual Brand Hotel<br />

03/16/2012<br />

23 1113 - 7 FACILITY FUEL-OIL PIPING