E. Dampers: Opposed blade volume dampers shall be provided for all sidewall-type supply<br />

air registers, sidewall-type exhaust air registers (installed on wall or in ceiling), and floor<br />

supply air registers, except as otherwise indicated or scheduled.<br />

2.04 LOUVERS:<br />

A. General: Except as otherwise indicated, provide manufacturer's standard 6” deep,<br />

stationary, drainable blade-type louvers with hidden vertical mullions, frame with integral<br />

caulking slots and sill extension, and aluminum bird screen, where shown; of sizes<br />

indicated; constructed of extruded aluminum; with components as indicated; and as<br />

required for complete installation. Louvers shall be Ruskin model ELF6375DX (extruded<br />

aluminum, 6” deep, 37½° fixed blades) or approved equivalent.<br />

B. Performance: Provide louvers that have a minimum of 50% free area (applicable to 48” x<br />

48” size) and a maximum pressure drop through the free area not exceeding that of those<br />

specified on drawings and schedules for each type as listed in manufacturer's current data.<br />

C. Substrate Compatibility: Provide louvers with frame and sill styles that are compatible with<br />

adjacent substrate, and that are specifically manufactured to fit into construction openings<br />

with accurate fit and adequate support, for weatherproof installation. Refer to general<br />

construction drawings and specifications for types of substrate which will contain each type<br />

of louver.<br />

D. Materials: Louver frames and blades shall be constructed of 0.080” thick aluminum<br />

extrusions, ASTM B-221, Alloy 6063-T5. Units shall be welded or assembled with stainless<br />

steel fasteners.<br />

E. Louver Screens: 3/4” square mesh anodized aluminum wire bird screen, mounted in<br />

removable extruded aluminum frame, shall be provided on inside face of exhaust air outlet<br />

louvers and outside face of outside air intake louvers.<br />

F. Finish: Color and finish type shall be as specified by Architect.<br />

PART 3 – EXECUTION<br />

3.01 INSPECTION:<br />

A. Examine areas and conditions under which air outlets and inlets are to be installed. Do not<br />

proceed with work until unsatisfactory conditions have been corrected.<br />

3.02 INSTALLATION:<br />

A. General: Install air outlets and inlets in accordance with manufacturer's written instructions<br />

and in accordance with recognized industry practices, to ensure that products serve intended<br />

functions.<br />

B. Coordinate with other work, including ductwork and duct accessories, as necessary to<br />

interface installation of air outlets and inlets with other work.<br />

Project No.: 10145<br />

550 15 th Street Dual Brand Hotel<br />

03/16/2012<br />

23 3713 - 4 DIFFUSERS, REGISTERS, AND<br />

GRILLES