2.03 FAN-POWERED TERMINALS:<br />

A. In addition to the above requirements for Air Terminals (Part 2.02), comply with the<br />

following:<br />

B. Fan section shall include a galvanized steel plenum, acoustically lined, housing a<br />

dynamically balanced fan with forward-curved blades, direct-driven from a permanent<br />

split-capacitor motor with SCR variable speed control, integral thermal overload<br />

protection, permanently-lubricated bearings, and fan contactor factory-wired to power and<br />

control terminal blocks in a sheet metal enclosure. Motor shall be specifically designed for<br />

use with an SCR for fan speed adjustment and shall include an anti-backward rotation<br />

device. Motor and fan shall be internally vibration-isolated from unit casing.<br />

1. For parallel variable air volume terminals, the fan shall be mounted in a separate<br />

compartment. The fan shall operate intermittently, drawing only plenum air. Unit<br />

shall include backdraft damper to prevent primary air from bypassing to the<br />

plenum. Damper shall be constructed of aluminum blades, gasketed to prevent<br />

leakage.<br />

2. For series constant volume terminals, the fan shall be mounted in a common<br />

compartment with the primary air damper. The fan shall operate continuously,<br />

drawing a mixture of plenum air and primary air.<br />

C. Fan controls shall be incorporated in a factory-assembled control panel and shall include<br />

pre-wired manual disconnect switch, a contractor, and a manually adjustable speed<br />

control for the fan, installed and wired by the terminal unit manufacturer.<br />

D. Units shall include filter rack and 1” thick throwaway filter, with side or rear access, on<br />

secondary air inlet. Provide two complete sets of filters.<br />

2.04 CONTROLS:<br />

A. Air terminal unit manufacturer shall mount DDC controller and actuator provided by<br />

temperature controls manufacturer. See Section 230900.<br />

PART 3 – EXECUTION<br />

3.01 INSPECTION:<br />

A. Examine areas and conditions under which air terminals are to be installed. Do not<br />

proceed with work until unsatisfactory conditions have been corrected.<br />

3.02 COORDINATION:<br />

A. The Contractor is responsible for determining the position of controls, actuators, and<br />

access. Coordinate each air terminal’s position with building elements, piping, conduit,<br />

ductwork and other items. Order left/right hand units as required, and inform all other<br />

trades as required. Relocate interfering items or terminal as required to provide proper<br />

access, if not coordinated beforehand.<br />

Project No.: 10145<br />

550 15 th Street Dual Brand Hotel<br />

03/16/2012<br />

23 3600 - 4 AIR TERMINAL UNITS