1. Steel Water Tanks:<br />

2.02 STEEL WATER TANKS:<br />

Project No.: 10145<br />

550 15 th Street Dual Brand Hotel<br />

03/16/2012<br />

a. A.O. Smith<br />

b. Raypak<br />

c. State<br />

d. PVI Industries<br />

e. Patterson-Kelley<br />

A. General: Provide steel water tanks of size, capacity, and orientation (vertical) as indicated<br />

on drawings.<br />

B. <strong>Construction</strong>: Hot-dipped galvanized steel, constructed with nontoxic welded joints, and<br />

rated for 125 psi working pressure.<br />

C. Lining: Interior of tanks shall be glass-lined and shall meet requirements of applicable<br />

regulatory standards for potable water tank linings.<br />

D. Support: Horizontal tanks shall be provided with steel saddles; vertical tanks with steel<br />

legs.<br />

E. Manholes: Manholes and covers shall be provided for tanks over 36” diameter, of sizes<br />

and locations as indicated.<br />

F. Tappings: Tappings shall be provided in sizes and locations as indicated; threaded<br />

female for 3” and smaller, flanged for 4” and larger.<br />

G. Accessories: Provide relief valve; pressure gauge; air volume operated controls; air<br />

charging connections; and gauge glass, brass fittings, compression stops, and heavy<br />

guard.<br />

PART 3 – EXECUTION<br />

3.01 EXAMINATION:<br />

A. Examine areas and conditions under which storage tanks are to be installed, and substrate<br />

which will support storage tanks. Do not proceed with work until unsatisfactory conditions<br />

have been corrected in a manner acceptable to Installer.<br />

3.02 INSTALLATION OF WATER TANKS:<br />

A. General: Install water tanks as indicated, in accordance with manufacturer’s installation<br />

instructions, and in compliance with applicable codes.<br />

B. Support: Set units on concrete pads, level and plumb.<br />

C. Make connections between water tanks and domestic water piping with isolation valves<br />

and dielectric unions or flanges, as indicated.<br />

22 1223 - 2 DOMESTIC WATER STORAGE<br />

TANKS