2.3 LUMINAIRE-MOUNTED PHOTOELECTRIC RELAYS<br />

A. Comply with UL 773 or UL 773A.<br />

B. Contact Relays: Factory mounted, single throw, designed to fail in the on position, and factory<br />

set to turn light unit on at 1.5 to 3 fc and off at 4.5 to 10 fc with 15-second minimum time<br />

delay. Relay shall have directional lens in front of photocell to prevent artificial light sources from<br />

causing false turnoff.<br />

1. Relay with locking-type receptacle shall comply with ANSI C136.10.<br />

2. Adjustable window slide for adjusting on-off set points.<br />

2.4 FLUORESCENT BALLASTS AND LAMPS<br />

A. Ballasts for Low-Temperature Environments:<br />

1. Temperatures 0 Deg F and Higher: Electronic type rated for 0 deg F starting and<br />

operating temperature with indicated lamp types.<br />

2. Temperatures Minus 20 Deg F and Higher: Electromagnetic type designed for use with<br />

indicated lamp types.<br />

B. Ballast Characteristics:<br />

1. Power Factor: 90 percent, minimum.<br />

2. Sound Rating: Class A.<br />

3. Total Harmonic Distortion Rating: Less than 10 percent.<br />

4. Electromagnetic Ballasts: Comply with ANSI C82.1, energy-saving, high power factor,<br />

Class P, automatic-reset thermal protection.<br />

5. Case Temperature for Compact Lamp Ballasts: 65 deg C, maximum.<br />

6. Transient-Voltage Protection: Comply with IEEE C62.41.1 and IEEE C62.41.2, Category A<br />

or better.<br />

C. Low-Temperature Lamp Capability: Rated for reliable starting and operation with ballast<br />

provided at temperatures 0 deg F and higher.<br />

2.5 BALLASTS FOR HID LAMPS<br />

A. Comply with ANSI C82.4 and UL 1029 and capable of open-circuit operation without reduction<br />

of average lamp life. Include the following features unless otherwise indicated:<br />

1. Ballast Circuit: Constant-wattage autotransformer or regulating high-power-factor type.<br />

2. Minimum Starting Temperature: Minus 22 deg F.<br />

3. Normal Ambient Operating Temperature: 104 deg F.<br />

4. Ballast Fuses: One in each ungrounded power supply conductor. Voltage and current<br />

ratings as recommended by ballast manufacturer.<br />

B. Auxiliary, Instant-On, Quartz System: Factory-installed feature automatically switches quartz<br />

lamp on when fixture is initially energized and when momentary power outages occur. System<br />

automatically turns quartz lamp off when HID lamp reaches approximately 60 percent of light<br />

output.<br />

Project No.: 10145<br />

550 15th Street Dual Brand Hotel<br />

03/19/2012<br />

265600 - 6 EXTERIOR LIGHTING