E. Solenoid enclosures shall meet the ICS-6 ANSI/NEMA standard and UL standards 429,<br />

508 and/or 1002 as follows:<br />

1. Type 1: General Purpose.<br />

2. Type 2: Drip proof.<br />

3. Type 3 and 3S: Raintight, dust tight and sleet (ice) resistant.<br />

4. Type 3R: Rainproof, sleet (ice) resistant.<br />

5. Type 4: Watertight and dust tight.<br />

6. Type 4X: Watertight, dust tight and corrosion resistant.<br />

7. Type 6: Submersible.<br />

8. Type 6P: Submersible, prolonged submersion at a limited depth.<br />

9. Type 7: Explosion proof, Class I, Division 1, Group A (acetylene); B (hydrogen); C<br />

(ethyl-ether vapors, ethylene or cyclopropane); D (gasoline, hexane, naphtha,<br />

benzene, butane, propane, alcohol, acetone, benzol, lacquer, solvent vapors or<br />

natural gas).<br />

10. Type 9: Dust-ignition proof, Class II, Group E (metal dust); F (carbon black coal<br />

or coke dust); G (flour starch or grain dust).<br />

11. Operating temperatures shall range from 185°F to 842°F for T1 through T6 code<br />

numbers.<br />

F. Parts in contact with fluid shall be brass, bronze, or stainless steel; core tube, 305 stainless<br />

steel; core and plug nut, 430°F stainless steel; seal, BUNA “N"; shading coil, copper; disc,<br />

BUNA “N" and Nylon; spring, 302 stainless steel (General Service).<br />

G. Manual reset safety shut-off valve shall open manually and close upon interruption of<br />

current.<br />

H. Electric current shall be AC of voltage shown on Division 26 drawings.<br />

2.11 Electric Valve Actuators:<br />

1. The valve actuator shall consist of a 120 volt, single phase, permanent split<br />

capacitor, reversible type electric motor which drives a compound epicyclic gear.<br />

A manual override handwheel shall be integral to the unit. The electric actuator<br />

shall have visual mechanical position indication, readable from a distance of 25<br />

feet, showing output shaft and valve position. Unit shall be capable of mounting<br />

directly to butterfly valve without brackets or adapters.<br />

2. The actuator shall have an integral terminal strip for wiring to power supplies.<br />

Cable entry shall be by means of two (2) 1” NPT threaded connections. Cable<br />

entries shall have UL recommended gland stops within the NPT hole to prevent<br />

glands from being screwed in too far and damaging cable.<br />

3. The actuator shall be constructed to withstand high shock and vibrations without<br />

operations failure. The actuator cover shall have captive bolts to eliminate loss of<br />

bolts when removing the cover from the base. One copy of the wiring diagram<br />

shall be provided with the actuator.<br />

4. Actuators with 600 in-lbs or more output torque shall have two adjustable factory<br />

calibrated mechanical torque limit switches of the single pole, double-throw type.<br />

Motor rotor shaft shall run in ball bearings at each end of the motor.<br />

5. The actuator housing shall be manufactured to NEMA 4 Standards and shall be<br />

UL recognized.<br />

6. The environmental temperature range of the actuator shall be -20ºF to +140ºF (-<br />

30°C to +60°C).<br />

Project No.: 10145<br />

550 15 th Street Dual Brand Hotel<br />

03/16/2012<br />

23 0523 - 6 GENERAL-DUTY VALVES FOR<br />

HVAC PIPING