K. Steel Flanges/Fittings: ANSI B16.5, ASTM A-234 (Fire Protection) including bolting and<br />

gasketing of the following material group, end connections and facings, except as<br />

otherwise indicated.<br />

Material Group: Group 1.1.<br />

End Connections: Buttwelding.<br />

Facings: Raised-face.<br />

L. Steel Pipe Flanges for Waterworks Service: AWWA C-207 (water service piping only).<br />

M. Corrosion-Resistant Cast Flanges/Fittings: MSS SP-51, including bolting and gasketing<br />

(threaded where pressure is not critical).<br />

N. Forged-Steel Socket-Welding and Threaded Fittings: ANSI B16.11, except MSS SP-79 for<br />

threaded reducer inserts; rated to match schedule of connected pipe (up to 4” pipe size).<br />

O. Wrought-Steel Buttwelding Fittings: ANSI B16.9, except ANSI B16.28 for short-radius<br />

elbows and returns; rated to match connected pipe.<br />

P. Stainless-Steel Buttwelding Fittings: MSS SP-43.<br />

Q. Stainless-Steel Vic Press 304 Fittings: Use with ½” through 2” Schedule 10S, Type<br />

304/304L stainless steel piping systems up to a maximum 500 psig. Precision cold drawn<br />

stainless steel fittings with Grade “H” HNBR suitable for potable water up to 210 deg. F or<br />

Grade “E” EPDM suitable for hot water up to 250 deg. F and pressure-sealed ends.<br />

R. Stainless-Steel Grooved End Fittings: ANSI /AWWA C606.<br />

S. Cast-Iron Threaded Drainage Fittings: ANSI B16.12.<br />

T. Forged Branch-Connection Fittings: Except as otherwise indicated, provide type as<br />

determined by Installer to comply with installation requirements.<br />

U. Pipe Nipples: Fabricated from same pipe as used for connected pipe; except do not use<br />

less than Schedule 80 pipe where length remaining unthreaded is less than 1-1/2” and<br />

where pipe size is less than 1-1/2”, and do not thread nipples full length (no closenipples).<br />

2.03 COPPER TUBE AND FITTINGS:<br />

A. Copper Tube: ASTM B-88; Type K or L as indicated for each service; hard-drawn<br />

tempered, except as otherwise indicated.<br />

B. DWV Copper Tube: ASTM B-306.<br />

C. ACR Copper Tube: ASTM B-280.<br />

D. Cast-Copper Solder-Joint Fittings: ANSI B16.18.<br />

E. Wrought-Copper Solder-Joint Fittings: ANSI B16.22.<br />

F. Cast-Copper Solder-joint Drainage Fittings: ANSI B16.23 (drainage and vent with DWV<br />

or tube).<br />

Project No.: 10145<br />

550 15th Street Dual Brand Hotel<br />

03/16/2012<br />

23 2113 - 4 HYDRONIC PIPING