PART 1 – GENERAL<br />

1.01 DESCRIPTION OF WORK:<br />

Project No.: 10145<br />

550 15 th Street Dual Brand Hotel<br />

03/16/2012<br />

SECTION 22 0719<br />

MECHANICAL INSULATION<br />

A. The work covered by this Specification consists of furnishing all labor, equipment,<br />

materials, accessories, and performance of all operations necessary for the installation of<br />

all insulation on all hot and cold surfaces of plumbing, piping, space heating and air<br />

conditioning systems in strict accordance with the specifications and applicable drawings.<br />

B. Types of mechanical insulation specified in this section include the following:<br />

1. Piping System Insulation:<br />

a. Fiberglass.<br />

b. Cellular Glass.<br />

c. Calcium Silicate.<br />

d. Thermal Ceramic.<br />

2. Equipment Insulation:<br />

a. Fiberglass.<br />

b. Calcium Silicate.<br />

c. 25/50 Rated Flexible Closed Cell Elastomeric.<br />

C. Refer to other Division 22 sections for requirements related to protection saddles,<br />

protection shields, thermal hanger shields, mechanical identification, and duct linings,<br />

which are not part of the work of this section.<br />

1.02 QUALITY ASSURANCE:<br />

A. Manufacturer's Qualifications: Firms regularly engaged in manufacture of mechanical<br />

insulation products and systems, of the types and sizes required, whose products have<br />

been in satisfactory use in similar service for not less than 3 years.<br />

B. Installer's Qualifications: Firm with at least 5 years of successful installation experience on<br />

projects with mechanical insulation. All insulation shall be installed per manufacturer’s<br />

recommendations by skilled workmen regularly engaged in this type of work.<br />

C. Furnish insulation systems to the project site bearing the manufacturer’s label with product<br />

identification.<br />

1.03 FIRE HAZARD RATING:<br />

A. All insulation products (including insulation, jacket, and adhesive used to adhere the jacket<br />

to the insulation) shall have composite Fire and Smoke Hazard ratings, as tested under<br />

procedures defined by ASTM E-84, NFPA 255 and UL 723, not exceeding:<br />

22 0719 - 1 PLUMBING INSULATION