E. Install pipe sleeve and seals at foundation and basement wall penetrations, as specified in<br />

Division 23, Section 232113, "Basic Piping Materials and Methods."<br />

F. Seal pipe penetrations of fire barriers using fire barrier penetration sealers specified in<br />

Division 23.<br />

G. Drips and Sediment Traps: Install a drip leg at points where condensate may collect, at<br />

the outlet of the gas meter, and in a location readily accessible to permit cleaning and<br />

emptying. Do not install drips where condensate is likely to freeze.<br />

1. Construct drips and sediment traps using a tee fitting with the bottom outlet<br />

plugged or capped. Use a minimum of 3 pipe diameters in length for the drip<br />

leg. Use same size pipe for drip leg as the connected pipe.<br />

H. Use fittings for all changes in direction and all branch connections.<br />

I. Install gas piping at a uniform grade upward to risers, and from the risers to the meter, or<br />

service regulator when meter is not provided, or the equipment.<br />

J. Connect branch outlet pipes from the top of horizontal lines, not from the bottom or sides.<br />

3.04 NATURAL GAS PIPING SPECIALTIES:<br />

A. Gas Meters:<br />

1. Install gas meter in accordance with local Utility company's installation<br />

instructions, and comply with requirements.<br />

B. Protective Coating:<br />

1. Provide protective coating on piping and fittings that will be in contact with<br />

material or atmosphere exerting a corrosive action, or piping buried in floors.<br />

C. Flexible Connectors:<br />

1. Provide flexible connectors with full size quick coupler for all kitchen and heavy<br />

moveable gas appliance equipment.<br />

2. Connectors shall be of lengths required to displace equipment for complete<br />

cleaning under and around gas appliance.<br />

D. Quick Couplers:<br />

1. Provide quick coupler at service end of flexible connectors.<br />

E. Valve Cabinets:<br />

3.05 VALVE APPLICATIONS:<br />

1. Provide valve cabinets for gas safety valves, mounted 5’-0” from floor to<br />

centerline. Control panels must be mounted to be visible from entry door of room<br />

or area within which panels are mounted.<br />

Project No.: 10145<br />

550 15 th Street Dual Brand Hotel<br />

03/16/2012<br />

23 1123 - 6 FACILITY NATURAL-GAS PIPING