PART 3 – EXECUTION<br />

3.01 EXAMINATION:<br />

flashing in the field. If the curbs are to have sound attenuation qualities, they shall be not less<br />

than those catalogued for the equipment specified.<br />

A. Examine areas and conditions, with Installer present, for compliance with requirements for<br />

installation tolerances, housekeeping pads, and other conditions affecting performance of<br />

fans.<br />

B. Do not proceed until unsatisfactory conditions have been corrected.<br />

3.02 INSTALLATION, GENERAL:<br />

A. Install fans level and plumb, in accordance with manufacturer's written instructions. Support<br />

units using vibration control devices as indicated. Vibration control devices are specified in<br />

Division 23 Section "Vibration Controls."<br />

1. Secure roof -mounted fans to roof curbs with cadmium-plated hardware.<br />

Project No.: 10145<br />

550 15 th Street Dual Brand Hotel<br />

03/16/2012<br />

a. Installation of roof curbs is specified in Division 7.<br />

2. Suspended Units: Suspend units from structural steel support frame using threaded<br />

steel rods and vibration isolation springs.<br />

B. Arrange installation of units to provide access space around air-handling units for service and<br />

maintenance.<br />

3.03 CONNECTIONS:<br />

A. Duct installations and connections are specified in other Division 23 sections. Make final duct<br />

connections on inlet and outlet duct connections with flexible connections.<br />

B. Electrical Wiring: Install electrical devices furnished by manufacturer but not specified to be<br />

factory-mounted. Furnish copy of manufacturer's wiring diagram submittal to Electrical<br />

Installer.<br />

1. Verify that electrical wiring installation is in accordance with manufacturer's submittal<br />

and installation requirements of Division -26 sections. Ensure that rotation is in<br />

direction indicated and intended for proper performance. Do not proceed with<br />

centrifugal fan start-up until wiring installation is acceptable to centrifugal fan<br />

Installer.<br />

2. Temperature control wiring and interlock wiring are specified in Division 23.<br />

3. Grounding: Connect unit components to ground in accordance with the National<br />

Electrical Code.<br />

3.04 FIELD QUALITY CONTROL:<br />

23 3413 - 9 HVAC FANS