8. AC Proof Status – Both Air and Water<br />

2.14 CONTROL SENSORS<br />

A. The unit shall be provided with the following factory mounted and wired control devices:<br />

1. Space Dry Bulb Temperature Sensor (field wired with economizer option)<br />

2. Space Relative Humidity Sensor (field wired with economizer option)<br />

3. Pool Water Temperature Sensor Defrost Controller<br />

4. Defrost Controller<br />

B. The unit shall be delivered with the following factory supplied sensors to be installed in the<br />

field:<br />

1. Cold Surface Condensation Prevention Temperature Sensor (Dew Point Reset).<br />

C. An anti-cycle timer shall be provided in the unit control system to prevent short-cycling of the<br />

compressor.<br />

D. Under normal conditions, the unit fan shall operate continuously, to provide air circulation within<br />

the pool enclosure.<br />

E. The compressor shall not operate if the defrost thermostat set point has been reached.<br />

Evaporator coil defrost shall be accomplished by the flow of air drawn across the coil by the unit<br />

fan.<br />

2.15 SEQUENCE OF OPERATION<br />

A. Description<br />

1. All essential operating and logic controls shall be factory mounted and wired in the unit.<br />

Control sequences shall be designed specifically to control swimming pool environmental<br />

conditions.<br />

B. Humidity Control<br />

1. When the humidity is above the set point the controller energizes the compressor and<br />

directs hot gas to air reheat condenser. If the pool water temperature is below the set<br />

point, the recovered heat is directed to the pool water condenser and the air reheat<br />

condenser or the auxiliary air cooling condenser, if so equipped. If the pool water<br />

temperature is at or above the set point, the recovered heat is directed to the air reheat<br />

condenser or the auxiliary air cooling condenser, if so equipped.<br />

C. Pool Water Heating<br />

1. When the dehumidifier is in either the dehumidifying and/or air conditioning mode and<br />

the pool water temperature is below the set point, a portion of the recovered heat is<br />

directed to the pool water condenser. At other times when the pool water requires heat, the<br />

PoolComPak activates the main pool water heater.<br />

D. Space Heating<br />

Project No.: 10145<br />

550 15 th Street Dual Brand Hotel<br />

03/16/2012<br />

23 8416 - 7 MECHANICAL DEHUMIDIFICATION<br />

UNITS