Project No.: 10145<br />

550 15 th Street Dual Brand Hotel<br />

12/23/2011<br />

piping system, shall be in accordance with ANSI B16.25 with the following<br />

exceptions:<br />

a. No permanent backing rings shall be used.<br />

b. Use of consumable inserts is permitted and encouraged as a means of<br />

obtaining required weld quality.<br />

10. Spacers may be used in fitting up pipe and weld fittings for tack welding to a<br />

proper gap for full penetration welds. Small tack welds which penetrate to the<br />

bottom of the welding groove shall be used. Tack welds lacking full penetration<br />

are not acceptable and shall be removed.<br />

11. All pipe welds that allow visual inspection on the inside and that can be reached<br />

by hand shall be inspected by the welder immediately after welding, and the<br />

following actions shall be taken:<br />

a. Weld spatter, flux, and debris shall be removed.<br />

b. Excessive penetration shall be removed by grinding.<br />

c. Areas without penetration or fusion shall be ground to sound metal and<br />

repair welded.<br />

12. Cleaning of excessive flux shall be performed between welding passes using wire<br />

brushing or grinding.<br />

13. Flanges welded to pipe spools shall be oriented with the bolt-holes straddling the<br />

centerlines established on the piping drawings. Take precautions throughout<br />

fabrication not to mar the gasket face on flanges.<br />

F. Domestic water Piping: Provide dielectric unions at all junctions of dissimilar metals.<br />

G. Flanged Joints: Match flanges within piping system, and at connections with valves and<br />

equipment. Clean flange faces and install gaskets. Tighten bolts to provide uniform<br />

compression of gaskets.<br />

H. Hubless Cast-Iron Joints: Comply with coupling manufacturer's installation instructions.<br />

3.04 EXPOSED PIPING IN FINISHED AREAS:<br />

A. Plumbing piping and fittings which are exposed (and uninsulated) in finished areas<br />

generally occupied by people, shall be installed with a smooth, high polish, durable<br />

chrome-plated finish.<br />

3.05 GROOVED PIPING SYSTEMS:<br />

A. All changes in direction shall be made with radius type elbows.<br />

1. Use long radius (R=1.5D) fittings wherever possible.<br />

2. Angles less than 22-1/2° may be made with pre-manufactured mitered fittings.<br />

3. Use of the angular deflection capabilities of grooved pipe couplings for intentional<br />

changes of direction shall not be allowed.<br />

B. All changes in pipe size shall be made with reducing fittings, not bushings or reducing<br />

couplings.<br />

22 1116 - 13 BASIC PLUMBING PIPING