C. Specification “C”, Flexible Fiberglass Equipment Insulation: ASTM C-553, Type I, 1.5 lb.<br />

per cu. ft. density. “k” factor shall be a maximum of 0.45 at 250° F mean temperature,<br />

450° F temperature limit.<br />

D. Specification “D”, Calcium Silicate Equipment Insulation: ASTM C-533, Type I, block-type.<br />

“k” factor shall be a maximum of 0.87 at 1000° F mean temperature, compression<br />

strength of 200 psi for 5% compression, and minimum transverse strength 60 psi.<br />

E. Specification “E”, Flexible Closed Cell Elastomeric Insulation: ASTM C-534, Type I. “k”<br />

value shall be a maximum of 0.27 at 75° F mean temperature, 220° F temperature limit,<br />

and water vapor permeability of 0.10 perm or less.<br />

F. Jacketing Material for Equipment Insulation: Provide presized glass cloth jacketing<br />

material, not less than 7.8 ounces per square yard, or metal jacket at Installer's option,<br />

except as otherwise indicated.<br />

G. Equipment Insulation Compounds: Provide adhesives, cements, sealers, mastics and<br />

protective finishes as recommended by insulation manufacturer for the applications<br />

indicated.<br />

H. Equipment Insulation Accessories: Provide staples, bands, wire, wire netting, tape, corner<br />

angles, anchors and stud pins as recommended by insulation manufacturer for the<br />

applications indicated.<br />

PART 3 – EXECUTION<br />

3.01 INSPECTION:<br />

A. Examine areas and conditions under which mechanical insulation is to be installed. Do<br />

not proceed with work until unsatisfactory conditions have been corrected in a manner<br />

acceptable to Installer.<br />

B. Workmanship shall be first class and of the highest quality. Poor installation or<br />

unacceptable appearance, as determined by the Engineer, shall be due cause to reject the<br />

entire project in whole, and retainage will be withheld until corrective action is completed<br />

to the Engineer's satisfaction.<br />

3.02 PIPING SYSTEM INSULATION:<br />

A. All portions of the following piping systems shall be insulated with Specification “A”<br />

Fiberglass Piping Insulation. See Table 1 for minimum insulation thicknesses required.<br />

1. Piping systems to be insulated:<br />

Project No.: 10145<br />

550 15 th Street Dual Brand Hotel<br />

03/16/2012<br />

a. Domestic cold water piping.<br />

b. Non-potable cold water piping.<br />

c. Domestic chilled water piping.<br />

d. Domestic hot water: supply, recirculated and tempered.<br />

e. Interior horizontal storm water and overflow drain piping below roofline,<br />

including roof drain bodies.<br />

f. Pumped storm water piping exposed to weather, horizontal and vertical.<br />

22 0719 - 4 PLUMBING INSULATION