constructed in accordance with UL 343, and be UL listed and bear the UL label. Pump set<br />

shall be duplex/simplex completely factory pre-piped and mounted on a skid drip pan<br />

ready to install. Each pump shall have the following:<br />

1. Oil pressure relief valve and return to suction piping.<br />

2. Belt/Coupling guard<br />

3. Back pressure regulating valve (shipped loose; installed by M.C.)<br />

4. Discharge check valve<br />

5. Discharge manual valve<br />

6. Suction side manual valve<br />

7. Compound pressure gauge on suction line with gauge cock.<br />

8. Strainer with isolation valves on each side of it.<br />

9. Pressure gauge or discharge with gauge cock.<br />

10. Cross over bridge piping on suction and discharge lines for parallel piping<br />

arrangement on duplex installation.<br />

11. Provide pressure measuring taps or both suction and discharge for pressure<br />

differential switch provided by others, coordinate with temperature control<br />

contractor.<br />

B. Drive: V-belt drive, with belt guard.<br />

C. Drive: Direct drive, close coupled.<br />

D. Motor: Split phase for single-phase motors; capacitor start, induction-run, totally enclosed<br />

for 3-phase motors.<br />

E. Controls: Controls shall include simplex/duplex factory prewired control panel consisting<br />

of H-O-A starter(s), thermal overload protection, auxiliary contacts for remote startstop.<br />

For duplex installation provide alternator and lead-lag control function.<br />

2.11 SUBMERSIBLE FUEL OIL PUMP:<br />

A. Pump shall be complete with the following:<br />

1. Check valve<br />

2. Air eliminator<br />

3. Expansion relief valve<br />

4. Syphon nozzle and venturi<br />

5. Syphon check valve and pressure test screw<br />

6. Accessible capacitor and electrical disconnect<br />

7. Leak detector head<br />

8. Bayonet-type electrical connector with explosion-proof electric disconnect without<br />

separating wires<br />

9. Pressure relief and check valves which can be isolated during a line pressure test.<br />

10. Tank and line test ports<br />

11. All leakage directed into storage tank.<br />

12. Hydraulically balanced Calcon impellers<br />

13. On-winding thermal overcurrent motor protection<br />

14. Permanent split-phase capacitor motor, 208-230 v single phase.<br />

B. Submersible pump(s) shall be as manufactured by Red Jacket Pumps a Marley Company.<br />

Capacity and model designation shall be as scheduled on drawings.<br />

Project No.: 10145<br />

550 15 th Street Dual Brand Hotel<br />

03/16/2012<br />

23 1113 - 6 FACILITY FUEL-OIL PIPING