deburred and cleaned. Pipe ends shall be marked at the required location to ensure full<br />

insertion into the coupling or fitting during assembly. Use a Victaulic "PFT" series tool with<br />

the proper sized jaw for pressing.<br />

3.04 GROOVED PIPING SYSTEMS:<br />

A. All changes in direction shall be made with radius type elbows.<br />

1. Use long radius (R=1.5D) fittings wherever possible.<br />

2. Angles less than 22-1/2° may be made with pre-manufactured mitered fittings.<br />

3. Use of the angular deflection capabilities of grooved pipe couplings for intentional<br />

changes of direction shall not be allowed.<br />

B. All changes in pipe size shall be made with reducing fittings, not bushings or reducing<br />

couplings.<br />

C. All branch outlets shall be made with Victaulic Style 920/920N Mechanical-T® bolted<br />

branch outlets for branches more than four pipe sizes smaller than the main, or Victaulic<br />

No. 25 or W25 grooved end reducing tees.<br />

D. Pipe shall be adequately laterally supported to prevent "pipe squirm." Provide a minimum<br />

of one hanger per pipe section. No pipe section shall be left unsupported between any<br />

two couplings.<br />

E. Risers more than 8’ high shall be made with rigid type couplings.<br />

F. Rigid style couplings shall be used in mechanical rooms, except where flexible style<br />

couplings are specifically allowed for thermal expansion compensation and/or vibration<br />

isolation, and to accommodate seismic movement.<br />

G. Flanges shall be standard welded slip-on or weld neck with a spool piece to a grooved<br />

end joint. "Flange adapters" are not allowed.<br />

H. Grooved pipe systems shall not be considered to be electrically conductive.<br />

1. Provide wire jumpers across all couplings where the piping system is required to<br />

be electrically conductive.<br />

I. Flexible couplings may be used for vibration elimination.<br />

1. Follow manufacturer’s recommendations.<br />

2. Provide 3 degrees of freedom by installing sufficient flexible couplings in different<br />

orientations.<br />

3. Use spring hangers for all sections of pipe intended for deflection.<br />

4. Roll-grooved fittings and pipe shall be considered to have 1/2 the deflection of<br />

cut-grooved fittings and pipe.<br />

J. Victaulic Style 177, 77 or W77 flexible couplings may be used in lieu of flexible connectors<br />

for vibration isolation at equipment connections. Three (3) couplings, for each connector,<br />

shall be placed in close proximity to the source of vibration.<br />

K. Grooved joint piping systems shall be installed in accordance with the manufacturer's<br />

guidelines and recommendations. All grooved couplings, fittings, valves, and specialties<br />

Project No.: 10145<br />

550 15th Street Dual Brand Hotel<br />

03/16/2012<br />

23 2113 - 14 HYDRONIC PIPING