e preset with a shear pin to allow vertical motion due to pipe expansion or contraction.<br />

Shear pin shall be removable and reinsertable to allow for selection of pipe movement.<br />

Guides shall be capable of ± 1-5/8” motion, or as required to meet specific location<br />

requirements. Pipe guides shall be type VSG as manufactured by Mason Industries, Inc.<br />

E. Flexible Pipe Connections: All equipment that is supported by or mounted on vibration<br />

isolators shall be piped with flexible connections. Specification “K” or Specification “L”<br />

flexible connections shall be installed parallel to the equipment shaft insofar as practical<br />

and on the equipment side of isolation valves.<br />

F. Equipment Isolation: All mechanical equipment shall be mounted on vibration isolators to<br />

prevent the transmission of vibration and mechanically transmitted sound to the building<br />

structure. Vibration isolators shall be selected in accordance with the weight distribution so<br />

as to produce reasonably uniform deflection. Isolator types shall be as noted on the<br />

equipment schedule below.<br />

EQUIPMENT VIBRATION ISOLATION SCHEDULE:<br />

(Not all types of equipment listed below are necessarily used on this project.)<br />

EQUIPMENT TYPE<br />

Floor-Mounted Pumps<br />

(Slab on Grade)<br />

Floor-Mounted Pumps<br />

Above/Below Occupied Spaces<br />

Structure-Hung Pumps<br />

* Omit if internal isolation is provided.<br />

** Omit for FPB without hydronic coil.<br />

*** Use type C mount for outdoor, wind-loaded installations.<br />

3.05 EXAMINATION OF RELATED WORK:<br />

Project No.: 10145<br />

550 15 th Street Dual Brand Hotel<br />

03/16/2012<br />

ISOLATOR SPECIFICATION<br />

Mount Type A;<br />

Connector Type K<br />

Base Type J; Spring Type B;<br />

Connector Type K<br />

Hanger Type D<br />

Connector Type K<br />

STATIC DEFLECTION<br />

(INCHES)<br />

A. Installer of vibration isolation work shall observe installation of other work related to<br />

vibration isolation work, including work connected to vibration isolation work; and, after<br />

completion of other related work (but before equipment start-up), shall furnish written<br />

report to Engineer listing any observed inadequacies which could prevent proper operation<br />

and performance of vibration isolation work. Report shall cover, but not necessarily be<br />

limited to, the following:<br />

0.75<br />

1.50<br />

0.75<br />

1. Equipment installations (performed as work of other sections) on vibration<br />

isolators.<br />

2. Piping connections, including flexible connections.<br />

3. Ductwork connections, including provisions for flexible connections.<br />

4. Passage of piping and ductwork, which is to be isolated, through walls and floors.<br />

B. Do not start up equipment until inadequacies have been corrected.<br />

22 0548 - 10 VIBRATION AND SEISMIC<br />

CONTROLS FOR PLUMBING<br />

PIPING AND EQUIPMENT