further protect against dust, moisture, and a chemical degradation. The windings<br />

shall comply with the latest applicable provisions of NEMA MG1.<br />

9. Motors shall have a clamp-type grounding terminal inside the motor conduit box.<br />

10. Motors with external conduit boxes shall have oversized conduit boxes.<br />

11. Maximum starting current shall be per NEMA MG1, Class H.<br />

12. Efficiency shall be per NEMA MG1 for Premium efficiency motors.<br />

13. Minimum insulation shall be Type F.<br />

14. Motors shall be random wound with copper coils.<br />

15. Motors located in a hazardous location shall be rated for the appropriate classification.<br />

B. It is intended that the Supplier use his standard motor on integrally constructed motor<br />

driven equipment such as appliances, hand tools, etc., which would otherwise require<br />

redesign of the complete unit in order to provide a motor having the specified features.<br />

C. Unless otherwise required by the detailed equipment specifications, motors within the<br />

horsepower ranges indicated below shall be rated and constructed as follows:<br />

1. Below 1/2 HP:<br />

a. 115 volt, 60 hz, single-phase.<br />

b. Dripproof in clean and dry locations; TEFP in all other locations.<br />

c. Permanently lubricated sealed bearings.<br />

d. Built-in manual-reset thermal protector; or furnished with integrally mounted<br />

stainless steel enclosed manual motor-overload switch.<br />

2. 1/2 to 1 HP:<br />

a. 230/460 volt, 60 hz, three phase.<br />

b. Dripproof in clean and dry locations; TEFC in all other locations.<br />

c. Permanently lubricated sealed bearings.<br />

3. 1-1/2 HP and Above:<br />

a. 230/460 [2<strong>08</strong>] volt, 60 hz, three phase.<br />

b. Dripproof in clean and dry locations; TEFC in all other locations.<br />

c. Oil or grease lubricated anti-friction or oil lubricated sleeve bearings.<br />

d. Vertical motors shall have fifteen year average life thrust bearings.<br />

D. Motors with horsepower ratings of 15 horsepower or greater shall be provided with space<br />

heaters to operate on 120 volt single-phase service.<br />

2.03 EQUIPMENT APPURTENANCES<br />

A. Cover belt or chain drives, fan blades, couplings, and other moving or rotating parts on all<br />

sides by a safety guard.<br />

1. Fabricate safety guards from 16 USS gage or heavier galvanized or aluminum-clad sheet<br />

steel or 1/2" mesh galvanized expanded metal.<br />

2. Design guards for easy installation and removal.<br />

3. Provide galvanized supports and accessories for each guard.<br />

4. Provide stainless steel bolts and hardware.<br />

5. Provide safety guards in outdoor locations designed to prevent the entrance of rain and<br />

dripping water.<br />

2.04 ANCHOR BOLTS<br />

Product Requirement – <strong>Bid</strong> <strong>Package</strong> #8 01 60 00-4<br />

Colorado River Municipal Water District<br />

Ward County Water Supply Expansion Project – <strong>North</strong> <strong>Well</strong> <strong>Field</strong><br />

5/24/2012