Colorado River Municipal Water District<br />

Raw Water Supply <strong>Well</strong> Sites<br />

Ward County <strong>North</strong> <strong>Well</strong> <strong>Field</strong><br />

B. GROUND CABLES: Stranded, bare tinned copper of 98% conductivity. Ground wire<br />

shall be Class B stranded tin-plated conductor without insulation in all cases where a<br />

single ground wire is indicated to be installed in a conduit with no other conductors in the<br />

conduit, or where the ground wire is directly buried in earth or concrete. In all other<br />

cases, insulate ground wire with green insulator as specified for low voltage wire.<br />

C. CONDUIT GROUND FITTINGS: Fittings for bonding ground cable to the conduit shall<br />

be FCI Burndy Corp., type NE or Thomas & Betts No. 3951 series.<br />

D. GROUND ROD BOXES: Precast Box with cast iron lid. Lid shall read “ground rod” on<br />

lid. Brooks Precast Model. “3-RT” or approved equal. Ground rod boxes located in<br />

driveway areas shall have an AASHO HS-20 rating.<br />

E. GROUND PLATE ELECTRODES: 20 gauge copper with terminated two (2) foot<br />

welded pigtail connection.<br />

F. EXOTHERMIC WELDING PROCESS: CADWELD MATERIALS – as manufactured<br />

by ERICO products or approved equal.<br />

2.2 PROCESSES<br />

A. All grounding system connections to building steel and ground rods shall be<br />

exothermically welded including all cable connections, and cable steel terminations. The<br />

use of mechanical type connectors is not acceptable.<br />

B. All materials involved must be from the same sources to insure compatibility.<br />

Connections made from this process shall meet the requirements of IEEE Standards 80<br />

and 837 and as listed in MIL 419 and other standards, National Electrical Code, etc.<br />

GROUNDING SYSTEM<br />

C. Provide a grounding system that includes all connections and the testing of ground rods,<br />

ground cables, ground buses, conduits, fittings, anchor supports, thermite process<br />

materials and equipment and other materials required for a complete installation.<br />

Grounding system shall be installed and sized in accordance with the National Electrical<br />

Code.<br />

PART 3 EXECUTION<br />

3.1 INSTALLATION<br />

A. Conductor Terminations and Connections:<br />

1. Pipe and Equipment Grounding Conductor Terminations: Bolted/clamp type<br />

connectors.<br />

2. Underground Connections: Exothermically welded connectors, except at test<br />

wells and as otherwise indicated.<br />

3. Connections to Ground Rods at Test <strong>Well</strong>s: Exothermically welded connectors.<br />

4. Connections to Structural Steel: Exothermically welded connectors.<br />

B. Ground electrical work in accordance with NEC Article 250 and local codes.<br />

May 18, 2012<br />

Grounding & Bonding for Electrical Systems<br />

Revision 0 26 05 26 - 2