C. System Components: The system will consist of the following major components and<br />

subsystems:<br />

1. Transmission Pump Station:<br />

a. One (1) PLC Modicon Quantum. The PLC shall be located in a NEMA 1, 14 gauge<br />

steel enclosure.<br />

1) One (1) Uninterruptible Power Supply (UPS)<br />

2) One (1) Touch screen<br />

3) Yagi antenna Fiber Optic Transceivers<br />

4) 2.4 GHz Radio Fiber Optic Patch Panels provided under Section 27 15 23 1<br />

“Communications Optical Fiber Horizontal Cabling”.<br />

5) One (1) Level Relay Panel in a NEMA 1, 14 gauge steel enclosure.<br />

6) One (1) Discharge Line Isolation Valve Relay Panel in a NEMA 1, 14 gauge steel<br />

enclosure.<br />

2. Base 21 Pump Station:<br />

a. Fiber Optic Transceivers<br />

b. Fiber Optic Patch Panels provided under Section 27 15 23 “Communications<br />

Optical Fiber Horizontal Cabling”.<br />

3. Odessa Pump Station:<br />

a. One (1) PLC Modicon Quantum. The PLC shall be located in a NEMA 1, 14 gauge<br />

steel enclosure.<br />

1) One (1) Uninterruptible Power Supply (UPS)<br />

2) One (1) Touch screen<br />

3) Yagi antenna<br />

4) 2.4 GHz Radio<br />

5) One (1) Level Relay Panel in a NEMA 1, 14 gauge steel enclosure.<br />

4. <strong>Well</strong> <strong>Field</strong> Pump Station:<br />

a. One (1) PLC Modicon Quantum. The PLC shall be located in a NEMA 1, 14 gauge<br />

steel enclosure.<br />

1) One (1) Uninterruptible Power Supply (UPS)<br />

2) One (1) Touch screen<br />

3) Yagi antenna Level Relay Controls in RTU Cabinet<br />

4) 2.4 GHz Radio Ethernet Radio<br />

5. Big Spring Pump Station:<br />

a. One (1) PLC Modicon Quantum. The PLC shall be located in a NEMA 1 NEMA 12, 14<br />

gauge steel enclosure.<br />

1) One (1) Uninterruptible Power Supply (UPS)<br />

2) One (1) Touch screen<br />

3) Yagi antenna<br />

4) 2.4 GHz Radio<br />

6. <strong>Well</strong> <strong>Field</strong> Sites (typ. of 21 sites):<br />

a. One (1) PLC Modicon Quantum Momentum. The PLC shall be located in a NEMA<br />

4X, 304 stainless steel enclosure.<br />

1) One (1) Uninterruptible Power Supply (UPS) Ethernet Radio<br />

2) Yagi antenna<br />

3) 2.4 GHz Radio<br />

Supervisory Control and Data Acquisition (SCADA) System 40 90 02-3<br />

CMD11269 – Ward County Transmission System Expansion – Contract C – Above Slab TPS, OPS, and WPS<br />

2

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!