25.10.2014 Views

Bid Package 08 North Well Field - Garney Construction

Bid Package 08 North Well Field - Garney Construction

Bid Package 08 North Well Field - Garney Construction

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Colorado River Municipal Water District<br />

Raw Water Supply <strong>Well</strong> Sites<br />

Ward County <strong>North</strong> <strong>Well</strong> <strong>Field</strong><br />

C. Install ground cables in conduits above grade or directly buried in earth to a depth of not<br />

less than 12" below grade. Installation to provide sufficient mechanical protection so as<br />

not to break ground cables or connections.<br />

D. Install ground cables continuously between connections. Splices shall not be permitted,<br />

except where indicated on the plans. Where ground cables pass through floor slabs,<br />

buildings, etc., and when not in metallic enclosures, provide a sleeve of approved, nonmetallic<br />

materials.<br />

E. Install a green-colored, equipment grounding conductor in raceways. Size conductors in<br />

accordance with NEC Article 250.<br />

F. Where ground wire is directly buried in earth or concrete, use standard bare tinned copper<br />

cable, in all other cases install a green-colored insulation, equipment grounding<br />

conductor. Size conductors in accordance with NEC Article 250. Provide grounding<br />

conductors as required per the NEC.<br />

G. Metal conduits stubbed up into switchgear, motor control center or other electrical<br />

equipment shall be terminated with insulated grounding bushings and connected to the<br />

equipment ground bus. Size the grounding wire in accordance with applicable sections of<br />

the National Electrical Code.<br />

H. Provide exothermic weld connection for extension to existing stub-up ground conductors.<br />

I. Bonding Straps and Jumpers: Install in locations accessible for inspection and<br />

maintenance, except where routed through short lengths of conduit.<br />

1. Provide grounding and bonding jumpers as required per the NEC.<br />

2. Bonding to Structure: Bond straps directly to basic structure, taking care not to<br />

penetrate any adjacent parts.<br />

3. Bonding to Equipment Mounted on Vibration Isolation Hangers and Supports:<br />

Install so vibration is not transmitted to rigidly mounted equipment.<br />

4. Use exothermic-welded connectors for outdoor locations, but if a disconnect-type<br />

connection is required, use a bolted clamp.<br />

J. Grounding and Bonding for Piping:<br />

1. Metal Water Service Pipe: Install insulated copper grounding conductors, in<br />

conduit, from building's main service equipment, or grounding bus, to main<br />

metal water service entrances to building. Connect grounding conductors to<br />

main metal water service pipes, using a bolted clamp connector or by bolting a<br />

lug-type connector to a pipe flange, using one of the lug bolts of the flange.<br />

Where a dielectric main water fitting is installed, connect grounding conductor<br />

on street side of fitting. Bond metal grounding conductor conduit or sleeve to<br />

conductor at each end.<br />

2. Water Meter Piping: Use braided-type bonding jumpers to electrically bypass<br />

water meters. Connect to pipe with a bolted connector.<br />

3. Bond each aboveground portion of gas piping system downstream from<br />

equipment shutoff valve.<br />

K. Bonding Interior Metal Ducts: Bond metal air ducts to equipment grounding conductors<br />

of associated fans, blowers, electric heaters, and air cleaners. Install a copper bonding<br />

jumper to bond across flexible duct connections to achieve continuity.<br />

May 18, 2012<br />

Grounding & Bonding for Electrical Systems<br />

Revision 0 26 05 26 - 3

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!