J. Acceptable RTU cabinet manufacturers:<br />

1. Hoffman<br />

2. Hammond<br />

3. Rittal<br />

2.09 LEVEL RELAY PANEL (TPS, OPS, WPS) & DISCHARGE LINE ISOLATION VALVE RELAY PANEL (TPS)<br />

A. Enclosure: The Level Relay Panels at TPS & OPS and the Discharge Line Isolation Valve<br />

Relay Panel at TPS shall be housed in a NEMA 1, 14 gauge steel enclosure. It shall have<br />

lifting eyes and a front door provided with a key locking handle. The Level Relay controls at<br />

WPS shall be located within the WPS RTU Cabinet.<br />

B. All switches, fuses, terminal blocks, etc., shall have permanent nameplates or labels for<br />

identification. All wiring shall be identified with wiring markers with alphanumeric<br />

characters. The identification of each wire shall be the same as that shown on the<br />

electrical schematic. Each wire shall be so identified at each end. Each end of every wire<br />

shall be provided with a heat shrinkable or equivalent sleeve-type wire marker-labeled in<br />

accordance with the electrical schematic. Use of adhesive and clip-on type markers is<br />

prohibited.<br />

C. Provide a print pocket pouch with the control schematic drawings on the inside of the Panel<br />

door. The control schematic drawings shall be the final version of the drawings and shall<br />

include any field revisions made during start-up.<br />

D. All relays and pushbuttons shall be NEMA rated, heavy duty type. IEC or dual IEC/NEMA<br />

rated equipment shall not be acceptable.<br />

E. Terminal strips shall be 600V, NEMA rated manufactured by Allen-Bradley, Phoenix Contact<br />

or approved equal. Distribution blocks shall be per Section 26 05 19.01, WIRE<br />

CONNECTIONS AND DEVICES.<br />

F. CONTROL RELAYS: Industrial type; contacts rated for 10 amps at 600 VAC; Allen-Bradley<br />

Bulletin 700 Type PK, Square D Class 8501 Type X, or approved equal. Relays shall have the<br />

capability of having contact decks added in the field. Contacts shall be field convertible to<br />

normally open or normally closed. Coils and contacts shall each be replaceable without<br />

replacing any other part of the relay. Where control relays are indicated on the Plans,<br />

industrial control relays shall be furnished whether the relay coil is operated with 120 VAC<br />

or 24 VDC. General purpose “plug-in” type relays shall not be acceptable.<br />

1<br />

G. INDICATING LIGHTS, SWITCHES, PUSHBUTTONS: Heavy duty and oil tight (30 mm); Square<br />

D Class 9001 or approved equal. Pilot lights shall be push to test (LED type) and shall be<br />

Square D SK or approved equal.<br />

H. Each relay panel shall include a 120VAC terminal block and circuit breaker.<br />

I. Acceptable RTU Relay Panel cabinet manufacturers:<br />

1. Hoffman<br />

2. Hammond<br />

3. Rittal<br />

Supervisory Control and Data Acquisition (SCADA) System 40 90 02-22<br />

CMD11269 – Ward County Transmission System Expansion – Contract C – Above Slab TPS, OPS, and WPS