Colorado River Municipal Water District<br />

Raw Water Supply <strong>Well</strong> Sites<br />

Ward County <strong>North</strong> <strong>Well</strong> <strong>Field</strong><br />

D. Install reinforcing steel in correct position by use of preformed bolsters, chairs, and<br />

spacers. Solid concrete blocks of appropriate size may be used to position bars in<br />

concrete placed on grade. Legs of steel supports that are in contact with form work shall<br />

be stainless steel or plastic tipped.<br />

E. All steel shall have a 2-inch minimum cover of concrete.<br />

F. Space bars properly and tie securely in position before placing concrete. Tack welding to<br />

keep reinforcing in place is not permitted. The spacings shown on the drawings for<br />

reinforcement and other embedded items are maximums. Provide and install a sufficient<br />

number of items so that the spacings shown are not exceeded. Locate the first and last<br />

items in a run of uniformly spaced items at not more than one-half the typical spacing nor<br />

12 inches from the end of a structural element.<br />

G. Locate reinforcement and other items to avoid conflict with the work of other trades.<br />

Provide additional reinforcement around openings as shown. Do not cut or remove<br />

reinforcement for any reason without the prior approval of the Engineer.<br />

H. Continuity of Vertical Reinforcement: No splices are permitted except as shown.<br />

Provide dowels from footings to walls or columns at all vertical bars in walls or columns.<br />

Except as otherwise shown, dowels shall have standard 90-degree ACI hooks with<br />

12-inch horizontal extensions and vertical legs of sufficient length to provide ACI<br />

Class B tension lap splices with the vertical bars.<br />

I. Continuity of Horizontal Reinforcement.<br />

1. Footings, walls, turned-down slab edges: Bars shall be lapped not less than<br />

32 bar diameters or 24 inches except where larger splices lengths are shown.<br />

Except where bar lengths are given, reinforcement is to be continuous for full<br />

length or width of member less required concrete covers. Do not splice<br />

transverse footing bars. Additional reinforcement shall be provided at corners,<br />

intersections, and other discontinuities as shown on the drawings.<br />

2. Concrete slabs-on-grade: Welded wire fabric shall be lapped not less than one<br />

and one-half meshes or 8 inches on all sides.<br />

3. Elevated slabs, beams: No splices except as shown.<br />

END OF SECTION<br />

May 18, 2012<br />

Concrete Reinforcement<br />

Revision 0 03 20 00 - 3