25.10.2014 Views

Bid Package 08 North Well Field - Garney Construction

Bid Package 08 North Well Field - Garney Construction

Bid Package 08 North Well Field - Garney Construction

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Colorado River Municipal Water District<br />

Raw Water Supply <strong>Well</strong> Sites<br />

Ward County <strong>North</strong> <strong>Well</strong> <strong>Field</strong><br />

13. For conductors that will be connected by others, provide at least 6 feet spare<br />

conductors in free standing panels and at least 2 feet spare in other assemblies.<br />

Provide additional spare conductor in any particular assembly where it is obvious<br />

that more conductor will be needed to reach the termination point.<br />

B. SPLICES<br />

1. Power Conductors: Splice in junction boxes or at outlets only for lighting and<br />

receptacle branch circuits. Splices for all other circuits shall be disallowed. All<br />

splices are subject to the Engineer’s approval. Obtain approval from Engineer<br />

before installing any splices.<br />

a. For existing installations, splices of 120V circuits shall use twist-on wire<br />

nuts.<br />

b. For splices of existing 480V circuits, the Contractor shall terminate the<br />

existing and new conductors using power distribution blocks mounted in<br />

a junction box.<br />

2. Control and Instrumentation Conductors: No splicing of control and<br />

instrumentation conductors shall be permitted between terminal points except as<br />

specifically indicated on the plans.<br />

3. No splicing of conductors shall be performed in any below ground structure.<br />

4. Condulet type fittings shall not contain splices. Under no condition shall<br />

conductors of a different color be spliced together.<br />

5. For No. 10 and smaller, connect conductors with a twist-on spring wirenut. If a<br />

splice or tap is below 3' above the final grade, fill the spring connectors with an<br />

electrical insulating resin so that the resin encapsulates conductor and spring<br />

materials. Conductor splices and taps inside the MCC, VFDs, panels, etc. shall<br />

be on the terminal strips or power distribution blocks.<br />

6. For No. 8 and larger, connect conductors with a split bolt type of connector or a<br />

mechanical, set screw type connector. Wrap splices and taps with a single halflapped<br />

layer or rubber tape followed by successive layers of vinyl tape until a<br />

vinyl tape layer thickness of twice the original conductor insulation thickness is<br />

achieved. If splice or tap is below 3' above the finished grade, the tape or splice<br />

shall have a final outer coating or insulating resin.<br />

C. TERMINATIONS<br />

1. Conductors terminated on a screw termination shall have a crimp on type spade<br />

connector applied on the wire end, Panduit PanTerm or approved equal.<br />

2. Furnish and install power distribution blocks as required for tapping conductors<br />

at their load connection point with conductors of smaller size. Install power<br />

distribution blocks with the number of poles and sizes needed for connecting the<br />

phase, neutral, and ground conductors.<br />

3. Tighten all screws and terminal bolts using torque type wrenches and/or drivers<br />

to tighten to the inch-pound requirements of the NEC and UL.<br />

4. Use crimp connectors on all stranded conductors.<br />

5. Soldered mechanical joints insulated with tape will not be acceptable.<br />

6. SINGLE CONDUCTORS: Sufficient wire shall be left at outlets to make<br />

connections to equipment without straining. Light switches and receptacles shall<br />

be connected with pig-tails and crimp-on connectors.<br />

May 18, 2012<br />

Low Voltage Electrical Power Conductors & Cables<br />

Revision 0 26 05 19-6

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!