2.14 GIGABIT ETHERNET 3-PORT SWITCH<br />

A. The ethernet switch shall transmit and receive 1000 Mbs data over fiber optic cable for a<br />

maximum distance of 5 miles. The unit shall utilize LED’s to display POWER STATUS,<br />

TRANSMIT DATA STATUS and RECEIVE DATA STATUS. The unit shall have an operating<br />

voltage of 24VDC. The unit shall have a mean time between failures (MTBF) greater than<br />

100,000 hours.<br />

B. The ethernet switch shall operate in ambient conditions of 0 to 50°C temperature and 10 to<br />

95 percent relative humidity, non-condensing.<br />

C. The unit shall be as manufactured by Industrial Fiber Systems, Inc.<br />

2.15 MANAGED INDUSTRIAL ETHERNET SWITCH<br />

A. The managed industrial Ethernet Switch with gigabit-ethernet (1000 Mbit/s), a minimum of<br />

two (2) ports for single mode fiber optic fiber and a minimum of fourteen (14) ports for<br />

CAT5e cable. The unit shall utilize LED’s to display POWER STATUS, LINK STATUS, DATA, and<br />

ERROR. The unit shall have an operating voltage of 24VDC and include a redundant power<br />

supply. The unit shall a mean time between failures (MTBF) greater than 200,000 hours<br />

B. The Ethernet Switch shall operate in ambient conditions of 0 to 50°C temperature and 10 to<br />

95 percent relative humidity, non-condensing. The switch shall be suitable for DIN-rail<br />

mounting.<br />

C. The unit shall be an industrial managed Ethernet Mice as manufactured by Hirschmann.<br />

2.16 GRAPHIC USER INTERFACE (GUI) TOUCH SCREENS (TPS, OPS, WPS, BPS)<br />

A. Touch screens shall be 14-inch LCD terminals with full touch screen capabilities as 1<br />

manufactured by Allen Bradley PanelView Plus or approved equal. Each unit will be<br />

programmed to provide up to a minimum of five local control displays to monitor and<br />

control the functions assigned to the PLC’s. Automatic and local control interfaces shall be<br />

provided.<br />

B. One copy of the manufacturers touch screen development software will be included under<br />

this specification. The license for the software shall be registered to the Owner.<br />

C. Touch screen shall be mounted to the RTU enclosure at a maximum elevation of 5’-0” AFF,<br />

include the housekeeping pad in the mounting height.<br />

D. The Contractor shall provide all programming and all required interconnection cables for a<br />

complete and operational system.<br />

Supervisory Control and Data Acquisition (SCADA) System 40 90 02-25<br />

CMD11269 – Ward County Transmission System Expansion – Contract C – Above Slab TPS, OPS, and WPS