Colorado River Municipal Water District<br />

Raw Water Supply <strong>Well</strong> Sites<br />

Ward County <strong>North</strong> <strong>Well</strong> <strong>Field</strong><br />

6. CPT Spare Capacity: 100 VA minimum.<br />

7. Bimetallic Overload Relays:<br />

a. Inverse-time-current characteristic.<br />

b. Class 20 tripping characteristic.<br />

c. Heaters in each phase matched to nameplate full-load current of actual<br />

protected motor and with appropriate adjustment for duty cycle.<br />

d. Ambient compensated.<br />

e. Automatic resetting.<br />

8. Solid-State Overload Relay:<br />

a. Switch or dial selectable for motor running overload protection.<br />

b. Sensors in each phase.<br />

c. Class 10/20 selectable tripping characteristic selected to protect motor<br />

against voltage and current unbalance and single phasing.<br />

d. Class II ground-fault protection, with start and run delays to prevent<br />

nuisance trip on starting.<br />

e. Analog communication module.<br />

f. External overload reset push button.<br />

C. Combination Magnetic Controller: Factory-assembled combination of magnetic<br />

controller, overcurrent protective device, and disconnecting means.<br />

1. MCP Disconnecting Means:<br />

a. UL 489, NEMA AB 1, and NEMA AB 3, with interrupting capacity to<br />

comply with available fault currents, instantaneous-only circuit breaker<br />

with front-mounted, field-adjustable, short-circuit trip coordinated with<br />

motor locked-rotor amperes.<br />

b. Lockable Handle: Accepts three padlocks and interlocks with cover in<br />

closed position.<br />

c. Auxiliary contacts "a" and "b" arranged to activate with MCP handle.<br />

d. Current-limiting module to increase controller short-circuit current<br />

(withstand) rating to 65 kA.<br />

2.3 ACCESSORIES<br />

A. General Requirements for Control Circuit and Pilot Devices: NEMA ICS 5; factory<br />

installed in controller enclosure cover unless otherwise indicated.<br />

B. IEC or dual rated NEMA/IEC equipment shall not be acceptable.<br />

C. CONTROL RELAYS: Industrial type; contacts rated for 10 amps at 600 VAC; Square D<br />

Class 8501 Type X, Allen-Bradley Bulletin 700 type PK, or approved equal. Relays shall<br />

have the capability of having contact decks added in the field. Contacts shall be field<br />

convertible to normally open or normally closed. Coils and contacts shall each be<br />

replaceable without replacing any other part of the relay. Where control relays are<br />

indicated on the Plans, industrial control relays shall be furnished whether the relay coil<br />

is operated with 120 VAC or 24 VDC.<br />

D. ELAPSED TIME METER: Yokogawa Type 240, or approved equal. The meter shall be<br />

of the non-reset type for totalizing of hours and operating on 120 or 240 VAC, 60 Hertz.<br />

May 18, 2012<br />

Enclosed Controllers<br />

Revision 0 26 29 13 - 7