25.10.2014 Views

Bid Package 08 North Well Field - Garney Construction

Bid Package 08 North Well Field - Garney Construction

Bid Package 08 North Well Field - Garney Construction

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Colorado River Municipal Water District<br />

Raw Water Supply <strong>Well</strong> Sites<br />

Ward County <strong>North</strong> <strong>Well</strong> <strong>Field</strong><br />

7. PAIRED SHIELDED AND TRIAD SHIELDED CABLE: Ground paired<br />

shielded and triad shielded cables at the instrument panel or starter end only and<br />

insulate from ground elsewhere. The shield shall be continuous for the entire<br />

run. The paired shielded and triad shielded cable shall not be laced with or<br />

placed in the same conduit with power cables and digital control cables. Each<br />

termination of paired shielded or triad shielded cable shall be coated with silicone<br />

jelly after termination. The shield of pair shielded cable and triad shielded cable<br />

shall only be broken when the conductors are terminated on terminal strips. Each<br />

conductor and shield shall be landed on its own terminal. Sharing of shield shall<br />

not be allowed.<br />

D. GROUNDING<br />

1. Conduits and other raceway shall contain an equipment grounding conductor<br />

whether the raceway is metallic or not. Conduits, motors, cabinets, outlets, and<br />

other equipment shall be properly grounded in accordance with National<br />

Electrical Code requirements. Where ground wire is exposed to mechanical<br />

damage, install wire in rigid aluminum conduit. Make connections to equipment<br />

with solderless connections. All connections to ground rods shall be of the fused<br />

type utilizing an exothermic welding process.<br />

2. Ground metallic material, including but not limited to metallic raceway, metallic<br />

boxes and metallic enclosures. Where metallic material is not connected by<br />

raceway to a solid ground, connect the metallic material to the largest equipment<br />

grounding conductor, which it houses. Clean the metal surface under the<br />

grounding lug to bright metal. Grounding connections to motors shall be to the<br />

grounding stud, which shall be threaded into the stationary frame; Use Burndy<br />

KC Servit, or approved equal. The ground wire shall not be lugged to a<br />

mounting bolt.<br />

3. Ground wire shall be uninsulated tin plated copper sized as shown on the plans in<br />

all cases where a single ground wire is indicated to be installed in a conduit with<br />

no other conductors in the conduit, or where the ground wire is directly buried in<br />

earth or concrete. In all other cases, insulate ground wire with green insulation as<br />

specified for low voltage wire. Provide and size bonding conductors in<br />

accordance with the National Electrical Code.<br />

4. Provide a bare uninsulated ground wire to run the entire length of all cable trays.<br />

The contractor shall bond to each section and to every enclosure served by<br />

conductors routed through the cable tray system<br />

E. TESTING<br />

1. Testing: All testing required shall be per Specification Section 26 01 26,<br />

“Testing of Electrical Systems”.<br />

2. Perform tests and inspections and prepare test reports and submit to the<br />

Owner/Engineer prior to final inspection. Test reports shall be submitted as<br />

required by Specification Section 26 01 26, “Testing of Electrical Systems”. All<br />

test reports shall be submitted in one binder under Specification Section 26 01<br />

26, “Testing of Electrical Systems”.<br />

3. Tests and Inspections:<br />

a. After installing conductors and cables and before electrical circuitry has<br />

been energized, test for compliance with requirements.<br />

b. Perform each visual and mechanical inspection and electrical tests stated<br />

in NETA Acceptance Testing Specification. Certify compliance with<br />

test parameters.<br />

May 18, 2012<br />

Low Voltage Electrical Power Conductors & Cables<br />

Revision 0 26 05 19-7

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!