2.04 COAXIAL CABLE<br />

A. Coaxial cable shall meet the following requirements:<br />

Characteristic impedance:<br />

Outer Conductor:<br />

Inner Conductor:<br />

Dielectric:<br />

Seal:<br />

50 ohms<br />

Copper, annularly corrugated<br />

Copper<br />

Closed cell low loss foam<br />

Connector o-rings to seal out moisture<br />

1. Coaxial cable shall be Times Microwave LMR type or approved equal.<br />

2. Diameter of coaxial cable shall be sized as indicated on the drawings and so that<br />

feedline loss from the antenna-side of the coaxial surge suppressor to the antenna does<br />

not exceed 1dB for directional antennas and 2 dB for omni-directional antennas.<br />

Feedline losses shall be calculated at the operating radio frequency and shall include<br />

losses in cable and connectors. The minimum size coaxial cable provided from the<br />

panel to the antenna shall be ½” diameter unless larger size is shown on drawings.<br />

3. All coaxial connectors shall be Type-N connectors. Connectors shall be manufactured<br />

by the same cable manufacturer which furnishes the coaxial cable. Connectors shall be<br />

Andrews Corporation Heliax cable connectors, or approved equal. All connectors shall<br />

be constructed of brass or be silver plated as recommended by manufacturer.<br />

Connectors shall have o-ring seal.<br />

4. All connections shall be weatherproofed using 3M-brand cold shrink weatherproofing<br />

kit or approved equal cold shrink weather proofing kit.<br />

5. Provide a pre-made cable assembly of Times Microwave LMR coaxial cable to connect<br />

from the radio antenna port to the radio-side of the coaxial surge suppressor. Provide<br />

straight or angled N-type connectors as necessary to route cable assembly within panel<br />

without exceeding manufacturer’s recommended bend radius. The pre-made cable<br />

shall be assembled by the coaxial cable manufacturer and shall be shipped with a<br />

certification of assembly and testing.<br />

6. Cable hangers shall be Andrews Hanger Model 42396A-5 for 7/8” cable or 43211A for<br />

½” cable with Andrews Round Member Adapter Model 31670, or approved equal. The<br />

use of plastic tie wraps is not acceptable.<br />

2.05 COAXIAL GROUNDING KIT<br />

A. Grounding straps shall be solid copper for high current handling. <strong>Construction</strong> shall be of<br />

the non-braided type. Grounding cable shall have field attachable grounding lug with a twopart<br />

tape system for weatherproofing. Grounding kit shall be Andrew Corporation or<br />

approved equal.<br />

Supervisory Control and Data Acquisition (SCADA) System 40 90 02-18<br />