Colorado River Municipal Water District<br />

Raw Water Supply <strong>Well</strong> Sites<br />

Ward County <strong>North</strong> <strong>Well</strong> <strong>Field</strong><br />

B. Electrical box locations shown on Contract Drawings are approximate unless<br />

dimensioned. Verify locations of boxes and outlets prior to rough-in. Outlet locations<br />

may be modified to accommodate changes in door swings, space changes or to clear<br />

other interferences that arise or from job modifications. Make such modifications at no<br />

cost to the Owner as a matter of job coordination. Coordinate job conditions and notify<br />

the Engineer of discrepancies before proceeding with the installation of the work. Set<br />

wall boxes in advance of wall construction blocked in place, and secured. Set wall boxes<br />

flush with the finish. Install extension sleeves as required to extend boxes to finished<br />

surfaces.<br />

C. Unless otherwise noted, location of outlet boxes shall be as follows:<br />

Equipment or Outlets<br />

Toggle switches<br />

Receptacles<br />

Equipment or Outlets<br />

Flow/Level Transmitters<br />

Circular Chart Recorder<br />

Motor starters<br />

Control stations<br />

Manual starters<br />

Thermostats<br />

Telephone outlets<br />

Circuit protective devices<br />

* Above Finished Floor.<br />

Elevation *(A.F.F.)<br />

4'0"<br />

1'6"<br />

Elevation *(A.F.F.)<br />

5'5"<br />

5'5"<br />

5'0"<br />

4'0"<br />

5'0"<br />

4'0"<br />

1'6"<br />

6'6" to top of enclosure<br />

D. Locate and install boxes to allow access. Where installation is inaccessible, coordinate<br />

locations and sizes of required access doors in accordance with other sections of the<br />

specifications.<br />

3.2 INSTALLATION<br />

A. Do not install boxes back-to-back in walls. Provide minimum 6" separation, except<br />

provide minimum 24" separation in acoustic-rated walls.<br />

B. Locate boxes in masonry walls to require cutting of masonry unit corner only.<br />

Coordinate masonry cutting to achieve neat openings for boxes.<br />

C. Provide knockout closures for unused openings.<br />

D. Use multiple-gang boxes where more than one (1) device is installed together; do not use<br />

sectional boxes. Provide barriers to separate wiring of different voltage systems.<br />

E. Install boxes in walls without damaging wall insulation.<br />

F. Provide recessed outlet boxes in finished areas; secure boxes to interior wall and partition<br />

studs, position to allow for surface finish thickness. Use stamped steel stud bridges for<br />

flush outlets in hollow stud wall, and adjustable steel channel fasteners for flush ceiling<br />

outlet boxes.<br />

May 18, 2012<br />

Outlet Boxes<br />

Revision 0 26 05 33.03-2