Colorado River Municipal Water District<br />

Raw Water Supply <strong>Well</strong> Sites<br />

Ward County <strong>North</strong> <strong>Well</strong> <strong>Field</strong><br />

2.2 LEVEL RELAY PANEL<br />

A.<br />

B.<br />

C.<br />

D.<br />

E.<br />

F.<br />

Enclosure: It shall have lifting eyes and a front door provided with a key locking handle.<br />

All switches, fuses, terminal blocks, etc., shall have permanent nameplates or labels for<br />

identification. All wiring shall be identified with wiring markers with alphanumeric<br />

characters. The identification of each wire shall be the same as that shown on the<br />

electrical schematic. Each wire shall be so identified at each end. Each end of every<br />

wire shall be provided with a heat shrinkable or equivalent sleeve-type wire markerlabeled<br />

in accordance with the electrical schematic. Use of adhesive and clip-on type<br />

markers is prohibited.<br />

Panel wiring shall be as follows:<br />

1. Each conductor terminated under a screw head shall have a crimp on spade<br />

terminal applied to its end prior to its termination.<br />

2. Each conductor has its own number and no number is used more than once.<br />

3. The number of each wire is placed at both ends of the wire next to its end<br />

according to wire tagging instructions as specified in 26 05 19, “Low Voltage<br />

Electrical Power Conductors and Cables”.<br />

4. The wire numbers, as actually installed, match the numbers on the shop<br />

drawings, O&M manuals, wiring diagrams and interconnection diagrams for this<br />

instrument panel.<br />

5. Conductors run open shall be bundled and bound at regular intervals not to<br />

exceed 6" with nylon ties, or approved equal. Wires within a bundle are to be<br />

run parallel to one another and not twisted. Bundles shall have a uniform<br />

appearance, circular cross section, and shall be securely fastened to the panel<br />

framework. Conductors carrying different voltages that are from the same source<br />

may occupy the same wireway provided all are insulated for the maximum<br />

voltage of any conductor in the wireway. Wiring carrying voltages that originate<br />

at different source shall not run in the same wireway.<br />

6. A separate 120VAC Terminal Block and circuit breaker shall be provided for the<br />

cabinet.<br />

Provide a print pocket pouch with the control schematic drawings on the inside of the<br />

Panel door. The control schematic drawings shall be the final version of the drawings<br />

and shall include any field revisions made during start-up.<br />

All relays and pushbuttons shall be NEMA rated, heavy duty type. IEC or dual<br />

IEC/NEMA rated equipment shall not be acceptable.<br />

Terminal strips shall be 600V, NEMA rated manufactured by Allen-Bradley, Phoenix<br />

Contact or approved equal. Distribution blocks shall be per Section 26 05 19, “Low<br />

Voltage Electrical Power Conductors and Cables”.<br />

May 18, 2012<br />

Instrumentation<br />

Revision 0 40 90 01- 5